Chapter 13 - Current Protection Functions
1000
100
10
1
0.1
V00616
Figure 217: EPATR B characteristic shown for TMS = 1.0
5.3
SENSITIVE EARTH FAULT PROTECTION LOGIC
IN
ISEF>1 Current
928
CTS Block
1724
Inhibit ISEF>1
ISEF>1 Direction
VN
ISEF> VNpol Set
IN
Low Current
Residual voltage polarisation
833
VTS Slow Block
ISEF> Blocking
VTS Blocks IN>1
409
ISEF>1 Timer Blk
ISEF> Blocking
*
AR Blks ISEF>3
V00738
Figure 218: Sensitive Earth Fault Protection logic diagram
378
1
Current in Primary A (CT Ratio 100A/1A)
&
Directional
check
&
* Stages 3 and 4 only
EPATR Curve
10
&
&
100
1000
777
IDMT/ DT
671
Note: For the purpose of clarity , this diagram shows the first
relevant stage number for each signal and setting name .
P54x1i-TM-EN-1
P543i/P545i
IN>1 Start
IN>1 Trip