Figure 54: Offset Mho Characteristics - Impedance Domain; Offset Mho Characteristic For Earth Faults - GE MiCOM P40 Agile Technical Manual

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Chapter 7 - Distance Protection
Z(1+k
.I
/I
+k
ZN
N
ph
Then if healthy phase currents are much less then the current of the faulty phase and the mutual compensation is
disabled:
@ I
I
N
ph
so that
@ Z(1 + k
Z
replica
Thus the Z
plane representation of the characteristic becomes static.
LP
3.1.4

OFFSET MHO CHARACTERISTIC FOR EARTH FAULTS

The diagram below illustrates how the Offset Mho characteristic for earth-fault distance protection is created in
the impedance domain.
V02713
Figure 54: Offset Mho characteristics – impedance domain
The two signals provided to the comparator are:
S
= V - I.Z'
1
S
= V - I.Z
2
Operation occurs when the angle between the signals is greater than 90°.
The following diagram below how the Offset Mho characteristic for earth-fault distance protection translates to
the loop impedance domain.
142
.I
/I
)
ZM
M
ph
)
ZN
j
Z 
Z
-plane
X
1
Z
V
I
V
I
Z
90°
V
I
Z
R
P543i/P545i
P54x1i-TM-EN-1