Dip Switch Settings (6 Position) - GE NetworX Series Installation And Startup

Zone expander module
Table of Contents

Advertisement

DIP SWITCH SETTINGS (6 position)

VI.
The first thing that must be decided is the starting zone of this particular zone expander. The starting zone must be
on a boundary of eight (8) zones. The sixteen (16) zones for this module will move out from this starting position.
To set the starting zone, set the dip switch according to the table below:
THE POSITION OF ALL SWITCHES IS ONLY UPDATED WHEN THE NX-216E IS POWERED UP.
BEFORE YOU CHANGE THE POSITION OF THESE SWITCHES YOU MUST POWER DOWN THE EXPANDER.
Expander #
Starting Zone #
9
9
17
25
33
41
49
57
65
73
81
89
97
105
113
121
129
137
145
153
161
169
177
185
Dip switch 6
- Dip switch 6 is used to disable the second block of eight (8) zones on this zone expander. This can
be done if only an eight- (8) zone expander is required in a particular expander location. To disable the second
group of eight (8) zones on this expander, turn dip switch 6 on.
6
Switch 1
22
OFF
23
ON
16
OFF
17
ON
18
OFF
19
ON
20
OFF
21
ON
96
OFF
97
ON
98
OFF
99
ON
100
OFF
101
ON
102
OFF
103
ON
104
OFF
105
ON
106
OFF
107
ON
108
OFF
109
ON
110
OFF
111
ON
Switch 2
Switch 3
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
ON
Switch 4
Switch 5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
NX-216E Zone Expander