GE MiCOM P40 Agile Technical Manual page 346

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Chapter 11 - Autoreclose
Signal Name
DeadLineLockout
Dead Time Start Enable (22)
EVOLVE LOCK
Evolving Fault (20)
FLTMEM 2P
Fault Memory (15)
FLTMEM 3P
Fault Memory (15)
AR Initiation (11), 1-pole / 3-
INIT AR
pole Trip (13), AR In Progress
(16)
LastShot
Sequence Counter (18)
OKTimeSP
1-phase AR Dead Time (24)
Prot AR Block
AR Initiation (11)
Prot Re-op
Evolving Fault (20)
RESCB1ARSUCC
AR Reset Successful (37)
RESCB1LO
Reset CB Lockout (57)
RESPRMEM
1-pole / 3-pole Trip (13)
Prepare Reclaim Initiation
SETCB13PCL
(34)
Prepare Reclaim Initiation
SETCB1SPCL
(34)
Set CB1 CL
TAR2/3Ph
1-pole / 3-pole Trip (13)
TARA
1-pole / 3-pole Trip (13)
TARANY
1-pole / 3-pole Trip (13)
TARB
1-pole / 3-pole Trip (13)
TARC
1-pole / 3-pole Trip (13)
TMEM1Ph
1-pole / 3-pole Trip (13)
TMEM2/3Ph
1-pole / 3-pole trip (13)
310
Source Module
Autoreclose Lockout (55)
Autoreclose Lockout (55)
Autoreclose Lockout (55)
Autoreclose Lockout (55)
Evolving Fault (20)
Autoreclose Lockout (55)
Dead Time Start Enable (22)
Autoreclose Lockout (55)
Sequence Counter (18)
Evolving Fault (20)
CB Autoclose (32)
Reclaim Time (35)
Autoreclose Lockout (55)
Successful AR Signals (36)
Autoreclose Lockout (55)
Fault Memory (15)
Reclaim Time (35)
Successful AR Signals (36)
Reclaim Time (35)
Successful AR Signals (36)
Evolving Fault (20)
1-pole / 3-pole Trip (13)
CB Trip Time Monitor (53)
1-pole / 3-pole trip (13)
CB Trip Time Monitor (53)
Force 3-phase Trip (10)
1-pole / 3-pole Trip (13)
Evolving Fault (20)
1-pole / 3-pole Trip (13)
CB Trip Time Monitor (53)
1-pole / 3-pole Trip (13)
CB Trip Time Monitor (53)
AR In Progress (16)
1-phase AR Cycle Selection (19)
Autoreclose Lockout (55)
AR In Progress (16)
CB Trip Time Monitor (53)
Autoreclose Lockout (55)
Destination Module
Description
Signal to force the auto-reclose sequence to
lockout
Lockout for 2nd trip after the "Discrim Time" has
expired
A signal to indicate that the initiating fault
involved 2 phases
A signal to indicate that the initiating fault
involved 3 phases
Internally derived signal to initiate Autoreclose
(external triggers not included)
Idicates tha the Autoreclose sequence has
reached the last shot
The dead time for single pole Autoreclose is OK
Signal to block Autoreclose for selected host
protection elements
Signal to indicate that further protection
operation has occurred during Autoreclose
Reset the indication of successful Autoreclose
Reset the indication of lockout
Reset the signal that indicates the faulted phases
that initiated the Autoreclose
Three-phase close command to CB
Single-phase close command to CB
Set CB as closed
A 2-phase or 3-phase trip has initiated
Autoreclose
An A-phase trip has initiated Autoreclose
Any trip has initiated Autoreclose
A B-phase trip has initiated Autoreclose
A C-phase trip has initiated Autoreclose
Signal to remember that Autoreclose was
initiated by a single-phase fault
Signal to remember that Autoreclose was
initiated by a 2-phase fault or a 3-phase fault
P543i/P545i