Figure 53: Directional Mho Element Construction - Impedance Domain - GE MiCOM P40 Agile Technical Manual

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P543i/P545i
Z
1
j
X
Z
V02712
Figure 53: Directional Mho element construction – impedance domain
The two signals provided to the comparator are:
S
= V
1
S
= V - IZ
2
where (for an A-N fault for example) with residual compensation applied:
V = V
A
I = I
+ k
.I
A
ZN
N
where k
= (Z
- Z
) / 3Z
ZN
0
1
and if mutual compensation is applied:
I = I
+ k
.I
+ k
A
ZN
N
where k
= 3Z
/ 3Z
and is defined by two settings: kZm Mutual Set and kZm Mutual Angle.
ZM
M
1
Operation occurs when the angle between the signals is greater than 90°.
To obtain a Z
-plane representation in the directional Mho element construction, V is replaced with V
LP
replaced with I
+ k
.I
ph
ZN
N
mutual current compensation).
The two signals provided to the comparator in this case are:
S
= V
1
ph
S
= V
- I
.Z(1+k
2
ph
ph
We can define a replica impedance reach, Z
Z
= Z(1+k
replica
ZN
or if mutual compensation is applied:
P54x1i-TM-EN-1
Plane
V
I
90°
V
I
and is defined by two settings: kZN Res Comp and KZN Res Angle.
1
.I
ZM
M
, where V
and I
are the faulty phase voltage and current respectively (assuming no
ph
ph
.I
/I
)
ZN
N
ph
replica
.I
/I
)
N
ph
Z
Z
j 
X
Z
Z
R
, as:
Chapter 7 - Distance Protection
Plane
LP
k
I
I
ZN
N
ph
V
ph
Z
replica
90°
R
V
I
ph
ph
I
Z
ph
replica
and I is
ph
141