Figure 177: Autoreclose Modes Enable Logic Diagram (Module 9); Figure 178: Force Three-Phase Trip Logic Diagram (Module 10) - GE MiCOM P40 Agile Technical Manual

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Chapter 11 - Autoreclose
5.5.2
AUTORECLOSE MODES ENABLE LOGIC DIAGRAM
AR In Service
AR Enable CB
*
AR Mode
AR 1P
AR 1/3P
AR 3P
AR Opto
AR Mode 1P
AR Mode 3 P
Seq Counter = 0
Seq Counter = 1
V03309

Figure 177: Autoreclose Modes Enable logic diagram (Module 9)

5.6
AR FORCE THREE-PHASE TRIP LOGIC
Following single-phase tripping, while the Autoreclose cycle is in progress, and upon resetting of the protection
elements, tripping switches to three-phase.
Any protection operations that occur for subsequent faults while the Autoreclose cycle remains in progress will be
tripped three-phase.
5.6.1
AR FORCE THREE-PHASE TRIP LOGIC DIAGRAM
CB1 L SPAROK
AR DISABLED
CB ARIP
TARANY
Seq Counter = 1
Seq Counter = 2
Seq Counter = 3
Seq Counter = 4
AR Lockout
A/R CB Unhealthy
Inhibit AR
V03313

Figure 178: Force Three-phase Trip logic diagram (Module 10)

When a three-phase trip is forced, the DDB signal AR Force 3 pole is asserted.
5.7
AUTORECLOSE INITIATION LOGIC
Autoreclose initiation starts Autoreclose for a circuit breaker only if Autoreclose is enabled for the circuit breaker,
and the circuit breaker is in service. When an Autoreclose cycle is started, Autoreclose in progress (ARIP) is
indicated. The indication remains until the end of the cycle. The end of the cycle is signified by successful
Autoreclose, or by lockout.
322
&
1
1
&
&
1
&
&
1
&
&
&
&
&
1
P543i/P545i
CB1 LSPAROK
CB1L3 PAROK
* Defaults to High if not mapped in PSL
CB1 L SPAROK
AR Force 3 pole
P54x1i-TM-EN-1