Chapter 16 - Current Transformer Requirements
4
DISTANCE PROTECTION REQUIREMENTS
Zone 1 Reach Point Accuracy (RPA)
³ K
´ I
V
(1+ X/R)(R
k
RPA
fZ1
where:
●
V
= Required CT knee point voltage (volts)
k
K
= Fixed dimensioning factor = 0.6
●
RPA
●
I
= Maximum secondary phase fault current at Zone 1 reach point (A)
fZ1
X/R = Primary system reactance/resistance ratio
●
●
R
= CT secondary winding resistance
CT
R
= Single lead resistance from CT to IED
●
L
Zone 1 Close-up Fault Operation
An additional calculation must be performed for all cables and lines where the source impedance ratio (SIR) may
be less than SIR = 2.
³ K
V
I
k
max
fmax
where:
K
= Fixed dimensioning factor = 1.4
max
I
= Maximum secondary phase fault current
fmax
Then, the highest of the two calculated knee points must be used.
Note:
It is not necessary to repeat the calculation for earth faults, as the phase reach calculation is the worst-case for CT
dimensioning.
422
+ R
)
CT
L
´ I(R
+ R
)
CT
L
P543i/P545i
P54x1i-TM-EN-1