Remove the redundant Ethernet board. Set the last octet of IP address using the DIP switches. The available
range is 1 to 127.
Unused
V01022
8.
Once you have set the IP address, reassemble the IED, following theses instructions in the reverse order.
Warning:
Take care not to damage the pins of the ribbon cable connector on the front panel when reinserting
the ribbon cable.
5.8

PRP/HSR CONFIGURATOR

The PRP/HSR Configurator tool is intended for MiCOM Px4x IEDs with redundant Ethernet using PRP (Parallel
Redundancy Protocol), or HSR (High-availability Seamless Redundancy). This tool is used to identify IEDs, switch
between PRP and HSR or configure their parameters, configure the redundancy IP address, or configure the SNTP
IP address.
5.8.1
CONNECTING THE IED TO A PC
Connect the IED to the PC on which the Configurator tool is used. This connection is done through an Ethernet
switch or through a media converter.
P54x1i-TM-EN-1
1
Example address
decimal 85
2
4
8
16
32
64
ON
SW2 Top view
1 + 4 + 16 + 64 = 85
Chapter 22 - Communications