Chapter 7 - Distance Protection
V02723

Figure 72: Reverse impedance reach line construction

For an Offset zone, Z' is the settable reverse reach. For a directional zone Z' is a fixed percentage (either 25% or
100%) of the forward reach (Z) in the opposite direction.
The signals provided to the comparator are:
S
= V - I.Z'
1
Ð -3°
S
= I.
2
Impedance on the tripping side of the Reverse Impedance Reach line is detected when the angle between S1 and
S2 is greater than 0°.
3.3.3

PHASE FAULT RESISTIVE REACH LINE

Refer to the following figure:
Network
V02725

Figure 73: Resistive reach of phase elements

164
+jX
+Z'
V / I
V / I - Z'
IED
Dist
Bus
Z
F
+R
-3°
V
I
Half of the loop
A
R
LP
B
C
P543i/P545i
Line
P54x1i-TM-EN-1