Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P543i/P545i
Chapter 9 - Non-Aided Schemes
Partial cross polarisation is therefore substituted for the normal memory polarising, for the duration of the TOC
Delay. If insufficient polarising voltage is available, a slight reverse offset (approximately 10% of the forward reach)
is included in the Zone 1 characteristic to enable fast clearance of close up three-phase faults.
P54x1i-TM-EN-1
263