DIRECTION OF FORWARD CURRENT FLOW (NOTE 8)
A
B
C
A
a
A
P2
P1
A
S2
S1
B
C
B
C
PARALLEL LINE
PROTECTION
NOTES 1.
C.T. SHORTING LINKS
(a)
(b)
PIN TERMINAL (P.C.B. TYPE)
50 OHM BNC CONNECTOR
9-WAY & 25-WAY FEMALE D-TYPE SOCKET
Issue:
Revision:
FIELD VOLTAGE OUTPUT REMOVED. CID HONG-98JC6A.
E
Date:
28/06/2013
Name:
N.JOHNSON
CAD DATA 1:1 DIMENSIONS: mm
DO NOT SCALE
Date:
Chkd:
A
P2
P1
S2
S1
C
B
PHASE ROTATION
NOTE 6
MiCOM P543 (PART)
C1
5A
A
B
C
1A
NOTE 5.
C3
C4
5A
N
B
n
1A
C6
C7
5A
b c
C
1A
C9
C10
5A
M
NOTE 4
1A
C12
C13
5A
N
SENSITIVE
NOTE 2.
1A
C15
A
C19
B
C20
C21
C
N
C22
C23
V BUSBAR
(SEE NOTE 3.)
C24
2. USED FOR SEF PROTECTION. SENSITIVE SHOULD BE
DRIVEN FROM A CORE BALANCE CT WHEN SENSITIVE
SETTINGS ARE USED.
3. V BUSBAR ONLY REQUIRED IF CHECK SYNCHRONISM FUNCTION ENABLED.
4. MUTUAL CURRENT INPUT ONLY REQUIRED IF ENABLED
IN LINE PARAMETERS.
Substation Automation Solutions
D1
-
D2
OPTO 1
+
D3
-
D4
OPTO 2
+
D5
-
OPTO 3
D6
+
D7
-
OPTO 4
D8
+
D9
-
OPTO 5
D10
+
D11
-
OPTO 6
D12
+
D13
-
OPTO 7
D14
+
D15
-
OPTO 8
D16
+
D17
COMMON
D18
CONNECTION
F1
FIBRE OPTIC
-
COMMUNICATION
F2
OPTO 9
+
CURR DIFF
F3
-
F4
OPTO 10
+
F5
-
F6
OPTO 11
+
CONNECT TO P594
F7
-
OPTO 12
F8
+
F9
-
OPTO 13
F10
+
F11
-
OPTO 14
F12
+
F13
-
OPTO 15
F14
+
F15
-
F16
OPTO 16
+
F17
COMMON
F18
CONNECTION
5. C.T. CONNECTIONS ARE SHOWN 1A CONNECTED AND ARE TYPICAL ONLY.
N
6. REVERSE PHASE ROTATION IS ALSO SUPPORTED
7. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
8. WITH C.T. POLARITY SETTING 'STANDARD'.
Title:
EXTERNAL CONN DIAG:CURRENT DIFF.RELAY(60TE) 1 OR 3 POLE
TRIPPING,AUTO-RECLOSE,CHK SYNCH & HIGH BREAK RELAYS
Drg
ALSTOM GRID UK LTD
10P54303
No:
(STAFFORD)
MiCOM P543 (PART)
J17
-
EIA485/
NOTE 7
KBUS
PORT
J18
+
J16
SCN
*
J1
-
AC OR DC
x
J2
+
TX1
RX1
TX2
RX2
GPS
POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
*
Sht:
Next
Sht:
J11
WATCHDOG
J12
CONTACT
J13
WATCHDOG
J14
CONTACT
H1
RELAY 1
H2
H3
RELAY 2
H4
H5
RELAY 3
H6
H7
H8
RELAY 4
H9
H10
H11
RELAY 5
H12
H13
H14
RELAY 6
H15
H16
H17
RELAY 7
H18
G3
RELAY 8
G4
G7
RELAY 9
G8
HIGH BREAK
G11
CONTACTS
RELAY 10
G12
G15
RELAY 11
G16
1