Figure 124: Aided Delta Por Scheme - GE MiCOM P40 Agile Technical Manual

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P543i/P545i
DIR REV
DIR FWD
CB
OPEN
DIR FWD
TZ (T)
t
Z
E03520

Figure 124: Aided Delta POR scheme

6.2
AIDED DELTA BLOCKING SCHEME
The signalling channel is keyed from operation of the Delta Reverse elements. If the remote device has detected
Delta Forward, it operates after the trip delay if no block is received.
The logic is:
Send logic: Key channel if a Delta Fault Reverse condition is detected
Trip logic: Trip if a Delta Fault Forward condition is detected, AND a keyed channel signal is NOT received,
before the Aided Delta Delay timer expires.
This scheme is shown in the figure below.
P54x1i-TM-EN-1
G
1
CTX
CRX
Signalling
&
Equipment
&
Trip G
1
END G
0
DIR FWD
Z (T)
R
R
Z (T)
DIR FWD
Signalling
Equipment
Trip H
END H
Chapter 8 - Carrier Aided Schemes
H
DIR REV
DIR FWD
1
CTX
CRX
&
&
DIR FWD
1
TZ (T)
t
0
CB
OPEN
Z
239