Chapter 26 - Maintenance and Troubleshooting
3.7.6

IEEE C37.94 FAIL

This indicates a Signal Lost, a Path Yellow (indicating a fault on the communications channel) or a mismatch in the
number of N*64 channels used on either channel 1 or channel 2. Further information can be found in the
MEASUREMENTS 4 column.
3.8
PSL EDITOR TROUBLESHOOTING
A failure to open a connection could be due to one or more of the following:
The IED address is not valid (this address is always 1 for the front port)
Password in not valid
Communication set-up (COM port, Baud rate, or Framing) is not correct
Transaction values are not suitable for the IED or the type of connection
The connection cable is not wired correctly or broken
The option switches on any protocol converter used may be incorrectly set
3.8.1
DIAGRAM RECONSTRUCTION
Although a scheme can be extracted from an IED, a facility is provided to recover a scheme if the original file is
unobtainable.
A recovered scheme is logically correct but much of the original graphical information is lost. Many signals are
drawn in a vertical line down the left side of the canvas. Links are drawn orthogonally using the shortest path from
A to B. Any annotation added to the original diagram such as titles and notes are lost.
Sometimes a gate type does not appear as expected. For example, a single-input AND gate in the original scheme
appears as an OR gate when uploaded. Programmable gates with an inputs-to-trigger value of 1 also appear as
OR gates
3.8.2
PSL VERSION CHECK
The PSL is saved with a version reference, time stamp and CRC check (Cyclic Redundancy Check). This gives a
visual check whether the default PSL is in place or whether a new application has been downloaded.
3.9
REPAIR AND MODIFICATION PROCEDURE
Please follow these steps to return an Automation product to us:
1.
Get the Repair and Modification Return Authorization (RMA) form
An electronic version of the RMA form is available from the following web page:
www.gegridsolutions.com/contact
2.
Fill in the RMA form
Fill in only the white part of the form.
Please ensure that all fields marked (M) are completed such as:
Equipment model
Model No. and Serial No.
Description of failure or modification required (please be specific)
Value for customs (in case the product requires export)
Delivery and invoice addresses
Contact details
3.
Send the RMA form to your local contact
For a list of local service contacts worldwide,visit the following web page:
www.gegridsolutions.com/contact
712
P543i/P545i
P54x1i-TM-EN-1