Chapter 16 - Current Transformer Requirements
2

RECOMMENDED CT CLASSES

You can use Class X current transformers with a knee point voltage greater or equal to that calculated. You can
also use class 5P protection CT. These have a knee-point voltage equivalent, which can be approximated from the
following calculations:
´ ALF)/I
V
= (VA
k
where:
V
= Knee-point voltage
k
VA = Voltampere burden rating
ALF = Accuracy limit factor
I
= CT nominal secondary current
n
R
= CT resistance
CT
420
´ ALF ´ I
+ (R
)
n
CT
n
P543i/P545i