Out Of Service Led On At Power-Up - GE MiCOM P40 Agile Technical Manual

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P543i/P545i
Test
Error Code Identification
The following text messages (in English) are displayed if a
fundamental problem is detected, preventing the system
from booting:
Bus Fail – address lines
SRAM Fail – data lines
3
FLASH Fail format error
FLASH Fail checksum
Code Verify Fail
The following hex error codes relate to errors detected in
specific IED modules:
3.1
0c140005/0c0d0000
3.2
0c140006/0c0e0000
3.3
The last four digits provide details on the actual error.
The IED displays a message for corrupt settings and
4
prompts for the default values to be restored for the
affected settings.
The IED resets when the power-up is complete. A record
5
error code is displayed
3.4

OUT OF SERVICE LED ON AT POWER-UP

Test
Using the IED menu, confirm the Commission Test or Test
1
Mode setting is Enabled. If it is not Enabled, go to test 2.
Select the VIEW RECORDS column then view the last
2
maintenance record from the menu.
P54x1i-TM-EN-1
Check
Check
Chapter 26 - Maintenance and Troubleshooting
These messages indicate that a problem has been detected on the IED's
main processor board in the front panel.
Input Module (including opto-isolated inputs)
Output IED Cards
Other error codes relate to hardware or software problems on the main
processor board. Contact with details of the problem for a full analysis.
The power-up tests have detected corrupted IED settings. Restore the
default settings to allow the power-up to complete, and then reapply
the application-specific settings.
Error 0x0E080000, programmable scheme logic error due to excessive
execution time. Restore the default settings by powering up with both
horizontal cursor keys pressed, then confirm restoration of defaults at
the prompt using the Enter key. If the IED powers up successfully, check
the programmable logic for feedback paths.
Other error codes relate to software errors on the main processor
board.
If the setting is Enabled, disable the test mode and make sure the Out of
Service LED is OFF.
Check for the H/W Verify Fail maintenance record. This indicates a
discrepancy between the IED model number and the hardware. Examine
the Maint Data; cell. This indicates the causes of the failure using bit
fields:
Bit Meaning
The application type field in the model number does not
0
match the software ID
The application field in the model number does not match
1
the software ID
The variant 1 field in the model number does not match the
2
software ID
The variant 2 field in the model number does not match the
3
software ID
The protocol field in the model number does not match the
4
software ID
The language field in the model number does not match the
5
software ID
The VT type field in the model number is incorrect (110 V VTs
6
fitted)
The VT type field in the model number is incorrect (440 V VTs
7
fitted)
Action
Action
709