Figure 239: Rate Of Change Of Frequency Logic (Single Stage); Independent R.o.c.o.f Protection - GE MiCOM P40 Agile Technical Manual

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P543i/P545i
3

INDEPENDENT R.O.C.O.F PROTECTION

Where there are very large loads, imbalances may occur that result in rapid decline in system frequency. The
situation could be so bad that shedding one or two stages of load is unlikely to stop this rapid frequency decline. In
such a situation, standard underfrequency protection will normally have to be supplemented with protection that
responds to the rate of change of frequency. An element is therefore required which identifies the high rate of
decline of frequency, and adapts the load shedding scheme accordingly.
Such protection can identify frequency variations occurring close to nominal frequency thereby providing early
warning of a developing frequency problem. The element can also be used as an alarm to warn operators of
unusually high system frequency variations.
3.1
INDEPENENT R.O.C.O.F PROTECTION IMPLEMENTATION
The device provides four independent stages of protection. Each stage can respond to either rising or falling
frequency conditions. This depends on whether the frequency threshold is set above or below the system nominal
frequency. For example, if the frequency threshold is set above nominal frequency, the rate of change of frequency
setting is considered as positive and the element will operate for rising frequency conditions. If the frequency
threshold is set below nominal frequency, the setting is considered as negative and the element will operate for
falling frequency conditions.
The function uses the following settings (shown for stage 1 only - other stages follow the same principles).
df/dt Avg.Cycles calculates the rate of change of frequency over a fixed period of several cycles.
df/dt>1 Status: determines whether the stage is for falling or rising frequency conditions
df/dt>1 Setting: defines the rate of change of frequency pickup setting
df/dt>1 Time: sets the time delay
df/dt>1 Dir'n: sets the direction of change you wish to check (positive, negative, or both)
In addition, start, trip and timer block DDB signals are available for each stage, as well as an inhibit signal to inhibit
all four stages.
3.2
INDEPENDENT R.O.C.O.F PROTECTION LOGIC
df /dt>1 Status
Enabled
Frequency
V
determination
df /dt Avg . Cycles
df /dt>1 Setting
df /dt>1 Dir'n
Positive
Both
Negative
1370
Freq Not Found
1368
Freq High
Freq Low
1369

Figure 239: Rate of change of frequency logic (single stage)

P54x1i-TM-EN-1
df/dt
-1
×
1
1
1
Chapter 15 - Frequency Protection Functions
&
1
df/dt >1 Time
&
597
df/dt >1 Start
601
df /dt>1 Trip
V00869