Figure 194: Successful Autoreclose Signals Logic Diagram (Module 36); Figure 195: Autoreclose Reset Successful Indication Logic Diagram (Module 37) - GE MiCOM P40 Agile Technical Manual

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P543i/P545i
5.13.3
SUCCESFUL AUTORECLOSE SIGNALS LOGIC DIAGRAM
3P Reclaim TComp
1P Reclaim TComp
SETCB1SPCL
CB1OP1P
CB Closed 3 Ph
RESCB1ARSUCC
3P Reclaim TComp
1P Reclaim TComp
SETCB13PCL
CB1OP2/ 3P
CB Closed 3 Ph
V03358

Figure 194: Successful Autoreclose Signals logic diagram (Module 36)

5.13.4
AUTORECLOSE RESET SUCCESSFUL INDICATION LOGIC DIAGRAM
CB1 OPANY
AR Start
Res AROK by UI
Enabled
Reset AROK Ind
Yes
Res AROK by NoAR
Enabled
AR DISABLED
Ext Rst AROK
Res AROK by Ext
Enabled
Res AROK by TDly
Enabled
AROK Reset Time
CB1 ARSUCC
V03361

Figure 195: Autoreclose Reset Successful Indication logic diagram (Module 37)

5.14
CB HEALTHY AND SYSTEM CHECK TIMERS
This logic provides signals to cancel Autoreclose if the circuit breaker is not healthy (for example low gas pressure)
or system check conditions are not satisfied (for example required line & bus voltage conditions) when the scheme
is ready to close the circuit breaker.
At the completion of a dead time, the logic starts an Autoreclose healthy timer. If a circuit breaker healthy signal
becomes high before the Autoreclose healthy time is complete, the timer stops and, if all other relevant circuit
breaker closing conditions are satisfied, the scheme issues a circuit breaker Autoclose signal. If the circuit breaker
P54x1i-TM-EN-1
1
0
&
0.02S
&
1
1
0
&
0.02S
&
1
1
&
&
&
&
t
0
&
S
Q
RD
S
Q
R
&
S
Q
RD
S
Q
R
Chapter 11 - Autoreclose
CB Succ 1P AR
1
CB1ARSUCC
CB Succ 3P AR
1
RESCB1 ARSUCC
335