Figure 206: Three-Phase Autoreclose System Check Logic Diagram (Module 45) - GE MiCOM P40 Agile Technical Manual

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P543i/P545i
5.23.1
THREE-PHASE AUTORECLOSE SYSTEM CHECK LOGIC DIAGRAM
CB SC ClsNoDly
Enabled
CB SC CS1
Enabled
Check Sync 1 OK
CB SC CS2
Enabled
Check Sync 2 OK
CB SC DLLB
Enabled
Dead Line
Live Bus
CB SC LLDB
Enabled
Live Line
Dead Bus
CB SC DLDB
Enabled
Dead Line
Dead Bus
CB SC Shot 1
Disabled
Seq Counter = 1
CB SC all
Disabled
Ext CS OK
V03372

Figure 206: Three-phase Autoreclose System Check Logic Diagram (Module 45)

P54x1i-TM-EN-1
&
&
&
&
&
Note: If the DDB signal Ext CS OK is not mapped in PSL , it defaults to High .
&
&
Chapter 11 - Autoreclose
&
CB Fast SCOK
1
1
CB SCOK
347