GE MiCOM P40 Agile Technical Manual page 167

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P543i/P545i
Phase k1 = 30%
Phase k2 = 100%
Therefore, settings in primary/secondary values for each device can be calculated as follows:
Setting
Phase CT Primary
Phase CT Sec'y
Phase Is1 [p.u.]
Phase Is1 (Primary)
Phase Is1 (Secondary)
Phase Is2 [p.u.]
Phase Is2 (Primary)
Phase Is2 (Secondary)
Note:
Settings shown in primary values at ends A and B appear different compared with end C. This is not a problem as the currents
at ends A and B will be multiplied by the Correction Factor, when the differential calculation is done.
Susceptance settings for Ends A and B
With a VT ratio 275 kV/110 V and CT ratio 4000/5:
R
= 800
CT
R
= 2500
VT
m S
B = 310
Secondary susceptance = 310
Susceptance settings for End C
With a VT ratio 275 kV/110 V and CT ratio 1200/5:
m S
B = 310
Secondary susceptance = 310
P54x1i-TM-EN-1
End A
4000A
5A
0.2
0.2*4000 = 800A
0.2*5 = 1A
2
2*4000 = 8000A
2*5 = 10A
m S(R
m S
/ R
)= 968
VT
CT
m S(R
/ R
)= 3.22 mS
VT
CT
Chapter 6 - Current Differential Protection
End B
4000A
5A
0.2
0.2*4000 = 800A
0.2*5 = 1A
2
2*4000 = 8000A
2*5 = 10A
End C
1200A
5A
0.2
0.2*1200 = 240A
0.2*5 = 1A
2
2*1200 = 2400A
2*5 = 10A
131