Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P543i/P545i
The Event Value cell for this type of event is a 32 bit binary string representing the state of the relevant DDB
signals. These binary strings can also be viewed in the COMMISSION TESTS column in the relevant DDB batch cells.
Not all DDB signals can generate an event. Those that can are listed in the RECORD CONTROL column. In this
column, you can set which DDBs generate events.
2.1.7

SECURITY EVENTS

An event record is generated each time a setting that requires an access level is executed.
The event type description shown in the Event Text cell displays the type of change.
2.1.8
PLATFORM EVENTS
Platform events are special types of standard events.
The event type description shown in the Event Text cell displays the type of change.
P54x1i-TM-EN-1
Chapter 17 - Monitoring and Control
433