Figure 188: Dead Time Start Enable Logic Diagram (Module 22) - GE MiCOM P40 Agile Technical Manual

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Chapter 11 - Autoreclose
5.11.1
DEAD TIME START ENABLE LOGIC DIAGRAM
DT Start by Prot
Disable
Protection Reset
Protection Op
AR Start
OKTimeSP
OK Time 3P
ARIP
AR Initiation
Dead Line
3 PDTStart WhenLD
Enabled
Disabled
DT Start by Prot
Protection Reset
Disable
AR 1pole in prog
DTStart by CB Op
Disabled
Enabled
CB1OP1 P
CB Open 3 ph
V03337

Figure 188: Dead time Start Enable logic diagram (Module 22)

330
&
&
S
Q
1
R
0
0.02
&
1
&
&
1
1
&
&
1
1
&
&
P543i/P545i
DTOK All
Dead Line Time
t
S
DeadLineLockout
Q
0
R
1
DTOK CB 1P
1
DTOK CB 3P
P54x1i-TM-EN-1