Ethernet Functionality - GE MiCOM P40 Agile Technical Manual

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P543i/P545i
UINT16
UINT32
UINT8
7.4.8.1
IEC 61850 GOOSE CONFIGURATION
All GOOSE configuration is performed using the IEC 61850 Configurator tool available in the MiCOM S1 Agile
software application.
All GOOSE publishing configuration can be found under the GOOSE Publishing tab in the configuration editor
window. All GOOSE subscription configuration parameters are under the External Binding tab in the configuration
editor window.
Settings to enable GOOSE signalling and to apply Test Mode are available using the HMI.
7.4.9

ETHERNET FUNCTIONALITY

IEC 61850 Associations are unique and made between the client and server. If Ethernet connectivity is lost for any
reason, the associations are lost, and will need to be re-established by the client. The IED has a TCP_KEEPALIVE
function to monitor each association, and terminate any which are no longer active.
The IED allows the re-establishment of associations without disruption of its operation, even after its power has
been removed. As the IED acts as a server in this process, the client must request the association. Uncommitted
settings are cancelled when power is lost, and reports requested by connected clients are reset. The client must
re-enable these when it next creates the new association to the IED.
7.4.10
IEC 61850 CONFIGURATION
You cannot configure the device for IEC 61850 edition 1 using the HMI panel on the product. For this you must use
the IEC 61850 Configurator, which is part of the settings application software. If the device is compatible with
edition 2, however, you can configure it with the HMI. To configure IEC61850 edition 2 using the HMI, you must first
enable the IP From HMI setting, after which you can set the media (copper or fibre), IP address, subnet mask and
gateway address.
IEC 61850 allows IEDs to be directly configured from a configuration file. The IED's system configuration
capabilities are determined from an IED Capability Description file (ICD), supplied with the product. By using ICD
files from the products to be installed, you can design, configure and test (using simulation tools), a substation's
entire protection scheme before the products are installed into the substation.
To help with this process, the settings application software provides an IEC 61850 Configurator tool, which allows
the pre-configured IEC 61850 configuration file to be imported and transferred to the IED. As well as this, you can
manually create configuration files for all products, based on their original IED capability description (ICD file).
Other features include:
The extraction of configuration data for viewing and editing.
A sophisticated error checking sequence to validate the configuration data before sending to the IED.
Note:
Some configuration data is available in the IEC61850 CONFIG. column, allowing read-only access to basic configuration data.
7.4.10.1
IEC 61850 CONFIGURATION BANKS
There are two configuration banks:
Active Configuration Bank
Inactive Configuration Bank
P54x1i-TM-EN-1
Chapter 22 - Communications
591