Distance Protection - GE MiCOM P40 Agile Technical Manual

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P543i/P545i
12

DISTANCE PROTECTION

12.1
DEPENDENCY CONDITIONS
Some protection elements can be set to have dependencies on the availability of the protection communication
channel(s) and on the status of the voltage transformer supervision function (VTS).
If you are testing a distance model, the distance protection can be permanently enabled, or it can be set so that it
is only enabled in the event of a failure of the protection communications channel(s).
The overcurrent and earth faults elements can be permanently enabled, or can be set so that they are only
enabled:
in the event of a failure of the protection communications channel(s)
in the event of a VTS alarm
according to a logical combination of both conditions.
If these elements are enabled with a dependency upon the above conditions, it is necessary to simulate the
condition to test the correct operation of the protection function.
A communications failure can be simulated by setting the Test Loopback cell to Disabled and checking that the IED
raises a Comms Fail alarm.
At the end of the test, clear the communications alarms and reset the statistics.
A VTS alarm can be raised by applying a 3-phase voltage to the VT inputs and then removing one phase voltage
for a duration exceeding the VTS Time Delay setting.
At the end of the tests, clear the VTS alarm.
12.2
DISTANCE PROTECTION SINGLE-ENDED TESTING
If the distance protection function is being used, test the reaches and time delays.
1.
Check for any possible dependency conditions and simulate as appropriate.
2.
In the CONFIGURATION column, disable all protection elements other than the one being tested.
3.
Disable the current differential function, directly or indirectly:
a.
If the distance element is enabled without dependency, disable the current differential element
Current Diff.
b.
If the distance protection is enabled with dependency on communication channel failure, the current
differential element Current Diff should remain enabled and the communication should be disrupted
to cause a suitable failure of the current differential protection
4.
Make a note of which elements need to be re-enabled after testing
12.2.1
PRELIMINARIES
You should now connect the IED to equipment able to supply phase-phase and phase-neutral volts with current in
the correct phase relation for a particular type of fault on the selected characteristic angle. The facility for altering
the loop impedance (phase-to-ground fault or phase-phase) presented to the IED is essential.
P54x1i-TM-EN-1
Chapter 25 - Commissioning Instructions
667