Figure 35: Asymmetric Propogation Delay Times - GE MiCOM P40 Agile Technical Manual

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Chapter 6 - Current Differential Protection
tB3*
E02607

Figure 35: Asymmetric propogation delay times

The GPS synchronised values at terminal A (tA1, etc.) can be individually compared with those at terminal B (tB1,
etc.) to derive the bias and differential currents. The propagation delay times are not required for the derivation of
the bias and differential currents, but they can be calculated individually as tp1, and tp2, and they are stored for
potential use if GPS synchronisation fails.
104
ta
tA1
tA2
tp 1
tA3
tA4
tp 2
tA5
tA*
tA6
Relay A
P543i/P545i
tB1
tB2
tB*
tc
tB3
td
tB4
tB5
tB6
Relay B
P54x1i-TM-EN-1