Figure 94: Zone Timer Logic - GE MiCOM P40 Agile Technical Manual

Single breaker current differential (with distance)
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P543i/P545i
6.3.4.3
ZONE TIMER LOGIC
Standard Mode
Basic Scheme Mode
Standard
Zone 1 Start Gnd
Zone 1 Start Phs
Alternative Mode
Basic Scheme Mode
Alternative
1691
Any Dist Start
V02782

Figure 94: Zone timer logic

Note:
Although the diagram above shows zone 1 logic only, the logic for all other zones follows the same principals.
P54x1i-TM-EN-1
tZ1 Gnd. Delay
0
&
t
tZ1 Ph. Delay
0
&
t
tZ1 Gnd. Delay
0
&
t
tZ1 Ph. Delay
0
t
Chapter 7 - Distance Protection
1984
Z1 G time elapse
1985
Z1 P time elapse
1984
Z1 G time elapse
1985
Z1 P time elapse
191