Omicron Lab CT Analyzer User Manual page 91

Table of Contents

Advertisement

Specific parameters and settings displayed for IEC 60044-6
The following parameters are only displayed in the CT-Object card if the
standard IEC 60044-6 is selected.
Param.
Description
Rct
Specified secondary winding resistance.
Possible values: 0 to 3000 ohms or soft key ?
Default: ?
Kssc
Rated symmetrical short-circuit current factor.
Possible values: 1 to 300 or soft keys ?
12.5, 15, 17.5, 20, 25, 30, 40 or 50.
Default: ?.
Tp
Primary time constant.
Possible values: 0.000 to 5.000s or soft keys 20ms,
40ms, 60ms, 80ms, 100ms or 120ms.
T
depends on K as follows:
p
K
Dimensioning factor.
Possible values: 1 to 1572.
K depends on T
V-al
Rated equivalent excitation limiting secondary voltage.
Possible values: 0 to 9999V or soft key ?
Default: ?.
I-al
Accuracy limiting secondary excitation current.
Possible values: 0.03mA to 30A or soft key ?
Default: ?.
E1
User-defined e.m.f. to verify the excitation current at this
specific e.m.f.
Possible values: 0.1 to 20000V or soft key ?
Ie1
Maximum allowed excitation current at E
e.m.f.).
Possible values: 0.03mA to 30A or soft key ?
Ktd
Rated transient dimensioning factor.
Possible values: 1.0 to 2043 or soft key ?
Default: ?.
1
, 3, 5, 7.5, 10,
K 1
T
------------ -
=
p
ω
as described above for T
p
p
1
.
(user-defined
1
1
.
The CT Analyzer Test Cards
Available for
IEC 60044-6, class
TPS TPX TPY TPZ
1
x
x
.
x
x
x
x
x
.
x
1
x
.
x
2
.
x
3
.
x
x
x
x
x
x
x
x
x
89