Test Settings and Results

The following settings are required to perform a winding resistance test.
The following parameters show the results of the winding resistance test after
the test is finished.
Parameter
Description
T-meas
Winding temperature of the CT at the time of measurement.
Value used:
Ambient Temperature defined in the Settings (main menu).
If this temperature is not set correctly, the reference resistance
value (R
ref
correctly.
T-ref
Reference temperature, i.e, temperature the CT is specified for.
Value used:
Reference temperature defined in the Settings (main menu).
The winding resistance at reference temperature is calculated
from the winding resistance measured at ambient temperature
(T
) and the specified reference temperature.
meas
Parameter
Description
I-DC
Current used for measurement. Selected automatically, cannot
be changed by the user.
Secondary winding resistance measurement only:
If I
is between 0.1 and 1 A, I
sn
If I
is lower than 0.1 A, I
sn
Maximum value: 1 A.
Primary winding resistance measurement only:
Maximum value: 10 A.
V-DC
Measured voltage.
R-meas
Measured resistance at ambient temperature.
R-ref
Reference resistance (temperature-compensated resistance,
compensated to T
) at reference temperature will not be calculated
is automatically set to I
DC
is automatically set to 0.1 A.
DC
).
ref
The CT Analyzer Test Cards
sn
.
107