Polarity Check - Omicron Lab CT Analyzer User Manual

Table of Contents

Advertisement

8.5

Polarity Check

This measurement type is exclusively intended for polarity checks using
How to get there:
the CPOL polarity checker as described below. Do not use this mode for
Press the Main soft key in
any other measurements!
any test card
Main Menu:
Note: The Polarity Check measurement type requires the CPOL polarity
- New Quick-Test
checker from OMICRON (order number VEHZ 0650).
OK soft key
CT-Quick card:
Polarity Check is a predefined measurement type, intended especially for
Measurement Type:
checking a series of test points (e.g., the connecting terminals of the burden
Polarity Check
wiring) for correct polarity. For this purpose, the CT Analyzer injects a signal with
a special waveform similar to a saw-tooth signal with a different steepness for
the rising and the falling slope. The CPOL polarity checker from OMICRON
checks the polarity of the injected signal and provides a clear indication as to
whether the polarity is OK or not.
Checking the polarity using the Polarity Check measurement type is much faster
than conventional methods and can easily be performed by a single person.
To select the Polarity Check measurement type, use the
move the cursor to the Measurement Type field in the CT-Quick card and then
press the Polarity Check soft key.
Figure 8-6
For the Polarity Check measurement type, the CT-Quick card holds the
following measurement quantities:
CT-Quick card and Results card for the Polarity Check
measurement type
Parameter
Description
Output
The output signal type is fixed to "AC".
U/I
Operating mode of the internal signal generator: voltage or
current source. Fixed to "Current".
Amplitude
Current value of the polarity check signal. Adjustable by the
user.
Possible values: 0 to 7A. Default: 1.00A.
Using the Quick Test Feature
cursor key to
145