6.7.3

Test Results

The following test results are displayed in the lower part of the Ratio card. In
addition to the results displayed in the Ratio card you can view the ratio and
phase table pages described in section 6.7.4 on page 122 and 6.7.5 on page
123.
Parameter
Description
Ratio
Current ratio error (in %) at the specified primary current (I
burden.
Pol.
OK: Polarity OK, phase angle is in the range of 0° ± 45°.
Failed: Wrong polarity of the CT or wrong polarity of the
measurement leads.
ε
Composite error in % at the specified primary current (I
C
operating burden.
This parameter is only displayed if the IEC 60044-1 standard is
selected in the CT-Object card.
Phase
Phase displacement (in minutes) at the specified primary
current (I
N
Winding turns ratio.
ε
Turns ratio error acc. to IEC 60044-6 class TPS or IEC 60044-1
t
class PX.
RCF
Ratio correction factor.
This parameter is only displayed if the IEEE C57.13 standard is
selected in the CT-Object card.
TCF
Transformer correction factor.
This parameter is only displayed if the IEEE C57.13 standard is
selected in the CT-Object card.
) and burden.
p
The CT Analyzer Test Cards
) and
p
) and
p
121