Setting Up The Ct Analyzer; Preparing And Configuring The Test - Omicron Lab CT Analyzer User Manual

Table of Contents

Advertisement

CT Analyzer User Manual
4.1

Setting Up the CT Analyzer

4.2

Preparing and Configuring the Test

I/0
50
1. Set up the CT Analyzer as described in section 2.2 on page 22.
1. Proceed as follows to display the CT-Object card with a new CT test.
If the CT Analyzer is already switched on:
– If necessary, display the CT-Object card and then press the Main soft key
to display the main menu.
– In the main menu, select "New CT Test" and press the OK soft key to
initialize a new CT test.
– The display shows the CT-Object card, ready to start a test.
If the CT Analyzer is switched off:
– Switch the CT Analyzer on.
– After the boot process is finished, the green LED is on and the red LED is
off.
– The display shows the CT-Object card, ready to start a test.
2. For reasons of simplicity, we do not want to perform a residual magnetism
measurement in our example CT test described here. Press the Select
Cards soft key in the CT-Object card to open the Select Cards page. Check,
and if necessary make the following test card selection (see Figure 4-1):
The following test cards are required: CT-Object, Burden, Primary Winding
Resistance, Secondary Winding Resistance, Excitation, Ratio and
Assessment.
The Residual Magnetism test card is not required. Deselect it if necessary.
Figure 4-1
Select Cards page
When finished, press the Back soft key to return to the CT-Object card.