CT Analyzer User Manual
40
3. Connect the red "Output" socket and the red socket of input "Sec" of the
CT Analyzer to the other (ungrounded) side of the burden.
CT
Figure 2-18
Wiring for a polarity check of the burden wiring using Quick Test
and the CPOL polarity checker
Note: The CT Analyzer measures the voltage of the injected signal using input
"Sec". Therefore, you should always connect this input when using the Polarity
Check measurement type. The higher the resistance of the wiring checked (i.e.,
the burden wiring) or the current amplitude set on the CT Analyzer, the higher
the terminal voltage generated by this current!
Burden
CPOL
CPOL