Note: Please refer to the following sections for more information:
1.2.5

Inputs and Outputs

Figure 1-5
Section 2.3 on page 23 for information on how to connect the CT Analyzer to
a PC.
Chapter 5 on page 59 for general information on how to operate the
CT Analyzer.
Section 5.7 on page 65 for more detailed information about the
Setting Menu page.
Warning: While the red LED of the
the output and the measurement inputs.
Inputs and outputs of the CT Analyzer
key is flashing, voltage is applied at
I/0
Output
Generator output.
AC: 40V
, 5A
rms
rms
DC: 120V, 15A
Sec
Measurement input for secondary side of CT,
150V
max., 500kΩ input impedance
AC
Prim
Measurement input for primary side of CT,
30V
max., 150kΩ input impedance
AC
Introduction
15