Test Results; Connecting The Burden And Running The Burden Test - Omicron Lab CT Analyzer User Manual

Table of Contents

Advertisement

6.3.2

Test Results

The lower part of the Burden card shows the results of the burden test after the
test is finished.
6.3.3

Connecting the Burden and Running the Burden Test

1. Press the Select Cards key soft in the CT-Object card to open the Select
2. In the Burden card, use the default test current or enter the desired test
3. Execute the burden test as described in section 4.3 on page 52.
Possible test steps following the burden test:
Parameter
Description
I-meas
Current measured during the test.
V-meas
Voltage measured at the load during the test.
Burden and cos ϕ calculated from the measured quantities.
Burden /
ϕ
Cos
If the rated secondary current is not known, the result field will
only show "n/a" as long as I
Z
Impedance of the burden calculated from the measured
quantities.
Cards page. Enable the Burden test card in the Select Cards page. Press
the Back soft key to apply your test card selection and return to the
CT-Object card.
Figure 6-5
Select Cards page with Burden test card enabled
current to parameter "I-test".
Residual magnetism measurement, see section 6.4.2 on page 103.
Primary resistance measurement, see section 4.3, steps 4. & 5. on page 53.
CT test, see section 4.3, steps 6. to 11. on page 54, and sections 4.4 on page
55 and 4.5 on page 57.
The CT Analyzer Test Cards
is not defined.