9424200994 Rev N
Timing Verification (IG Mode)
Time Delay Range = 0 to 60,000 ms
Timing Accuracy = ±0.5% or ±½ cycle, whichever is greater + 3 cycles max for currents 1.5 x pickup
Step
Time Delay Setting
4
2,000 ms
5
5,000 ms
5
10,000 ms
BE1-11g
Low
Actual Timing
1,942 ms
4,927 ms
9,902 ms
High
2,058 ms
5,073 ms
10,098 ms
Instantaneous Overcurrent (50) Test
445
Pass/Fail
P / F
P / F