9424200994 Rev N
Operational Settings
Loss of excitation - reverse var based element operational settings are configured on the Loss of
Excitation - Reverse var Based (40Q) settings screen (Figure 82) in BESTCOMSPlus. Setting ranges and
defaults are summarized in Table 47.
Figure 82. Loss of Excitation - Reverse var Based Settings Screen
Setting
Mode
0 or 1 to 6,000 (5A CTs)
Pickup
0 or 1 to 1,200 (1A CTs)
Time Delay
BE1-11g
Table 47. Operational Settings
Range
Disabled or Enabled
0 or 1 to 600,000
Increment
Unit of Measure
n/a
varies
varies
Loss of Excitation - Reverse Var Based (40Q) Protection
Default
n/a
Disabled
vars
milliseconds
129
0
0