Digital Input Function: General Switch A-D; Digital Input Function: Capture Trace; Digital Input Function: Simulate Pre-Fault; Digital Input Function: Simulate Fault - GE 469 Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

4 SETPOINT PROGRAMMING
There are four General Switch functions assignable to any of the four assignable digital inputs. Once a General
Switch function is chosen for one of the digital inputs, the setpoint messages shown here follow the assign-
ment message. An alarm and/or trip may then be configured for that input. The alarm and/or trip may be
assigned a common name and a common block time from motor start if required (if the alarm is to be disabled
until some period of time after he motor has been started). A value of "0" for the BLOCK TIME indicates that the
feature is always active, when the motor is stopped or running. The switch may also be defined as normally
open or normally closed. After the block delay has expired, the digital input will be monitored. If the switch is
not in its normal state after the specified delay, an alarm or trip will occur.
This setting allows the user to capture a trace upon command via a switch input. The captured waveforms can
then be displayed with the 469PC software.
This setting allows the user to start Simulate Pre-Fault mode as programmed in S13 via a switch input. This is
typically used for relay or system testing.
This setting allows the user to start Simulate Fault mode as programmed in S13 via a switch input. This is typ-
ically used for relay or system testing.
This setting allows the user to start Simulate Pre-Fault to Fault mode as programmed in S13 via a switch input.
This is typically used for relay or system testing.
GE Power Management

4.4.18 DIGITAL INPUT FUNCTION: GENERAL SWITCH A-D

SWITCH NAME:
ESCAPE
General Sw. A
MESSAGE
GENERAL SWITCH A:
ESCAPE
Normally Open
MESSAGE
BLOCK INPUT
ESCAPE
FROM START: 0 s
MESSAGE
GENERAL SWITCH A
ESCAPE
ALARM: Off
MESSAGE
ASSIGN ALARM RELAYS:
ESCAPE
Alarm
MESSAGE
GENERAL SWITCH A
ESCAPE
ALARM DELAY: 5.0 s
MESSAGE
GENERAL SWITCH A
ESCAPE
EVENTS: Off
MESSAGE
GENERAL SWITCH A
ESCAPE
TRIP: Off
MESSAGE
ASSIGN TRIP RELAYS:
ESCAPE
Trip
MESSAGE
GENERAL SWITCH A
ESCAPE
TRIP DELAY: 5.0 s
MESSAGE

4.4.20 DIGITAL INPUT FUNCTION: SIMULATE PRE-FAULT

4.4.22 DIGITAL INPUT FUNCTION: SIMULATE PRE-FAULT...FAULT
469 Motor Management Relay
Range: 12 alphanumeric characters
Range: Normally Open, Normally Closed
Range: 0 to 5000 sec., step 1 (0 indicates that feature is active
while motor is stopped as well as running)
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3, Alarm
& Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3
Range: 0.1 to 5000.0 sec., step 0.1
Range: On, Off
Range: Off, Latched, Unlatched
Range: Trip, Trip & Auxiliary2, Trip & Aux2 & Aux3,
Trip & Auxiliary3
Range: 0.1 to 5000.0 sec., step 0.1

4.4.19 DIGITAL INPUT FUNCTION: CAPTURE TRACE

4.4.21 DIGITAL INPUT FUNCTION: SIMULATE FAULT

4.4 S3 DIGITAL INPUTS
4-23
4