How To Reset The Trip Lockout Function - ABB REF 610 Operator's Manual

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS755539
Main Menu
MEASUREMENTS
RECORDED DATA
OPERATION
SETTINGS
CONFIGURATION
INFO
Fig. 4.1.9.-1
Setting the real-time clock
4.1.10.
Feeder Protection Relay
Operator's Manual - ANSI Version
5. The first digit of the setting value of the parameter to be edited starts to flash.
Use
and
to move the cursor and
value. The setting range (for example Year or Minutes) is shown on the right-
hand side of the second line of the display.
6. To store a new value and return the display to the view mode, press
7. To exit the setting mode without storing the changes, press
confirming and the display is returned to the view mode.
8. Press
to return the display to the idle mode.
Group Menu
CONFIGURATION
FUNCTION TEST/DI
COMMUNICATION
LANGUAGE
MEMORY SETTINGS
FREQUENCY
HMI PASSWORDS
TIME
TRIP CIRCUIT SUP
STORE COUNTER

How to reset the trip lockout function

The trip lockout function is used to prevent accidental closing of the circuit breaker
after a trip. The trip lockout function must be locally reset with a separate reset
before the circuit breaker can be closed again.
Reset the trip lockout as follows:
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select OPERATION\TRIP LOCKOUT\LOCKOUT
RESET.
3. Press
to enter the setting mode. The second line starts to flash.
4. Press
to reset trip lockout.
5. Press
to return the display to the idle mode.
and
to increase or decrease the
Parameter Menu
CONFIGURATION
Confirm
YY-MM-DD
(00-23)
hh.mm;ss
(00-59)
Cancel
REF 610
REF 610
.
once before
A040238_2
23