The mode of all logical nodes located under CTRL logical device are set with Control
mode. Control mode is selected via the HMI or PCM600 path Configuration/
Control/General. By default, Control mode can only be set locally through
LHMI.Control mode inherits its value from Test mode but Control mode "On",
"Blocked" and "Off" can also be independently set. Control mode is also available via
IEC 61850 communication (CTRL.LLN0.Mod).
Table 9:
Control mode
Control mode
Description
On
Normal operation
Blocked
Control function commands blocked
Off
Control functions disabled
According to IEC 61850, the physical outputs to process should be blocked when
device is set to blocked or test blocked mode. The usage depends heavily on the actual
ACT configuration. In the protection blocking example the main trip from
TRPPTRC1 is blocked, and in the control blocking example the CBXCBR1 is
blocked. Both comply to the IEC 61850. In real applications some of PTRC's might
also be used for signalling purposes (GOOSE) and blocking and interlocking via IO.
The physical outputs to process can be blocked with "IED blocked" and "IED test and
blocked" modes. If physical outputs need to be blocked, the application configuration
must block signals or function blocks that affect primary apparatuses. Blocking
scheme needs to use the BEH_BLK output of the PROTECTION function block.
Protection
BI_SG_2
SG_LOGIC_SEL
BI_SG_3
SG_1_ACT
BI_SG_4
SG_2_ACT
BI_SG_5
SG_3_ACT
BI_SG_6
SG_4_ACT
SG_5_ACT
SG_6_ACT
BEH_TEST
BEH_BLK
GUID-CAF67CB2-774E-4122-A235-D07F8768B202 V1 EN
Figure 62:
Master trip TRPPTRC blocked using Protection function block
BEH_BLK

Control blocking example

The physical outputs to process can be blocked with "Blocked" mode. If physical
outputs need to be blocked, the application configuration must block signals or
function blocks that affect primary apparatuses. Blocking scheme needs to use
BEH_BLK output of CONTROL function block.
Protection and control engineering
TRPPTRC1
BLOCK
OPERATE
RST_LKOUT
output
Section 5
Control BEH_BLK
FALSE
TRUE
FALSE
TRIP
TRPPTRC1_TRIP
CL_LKOUT
89