Table 43. Residual overvoltage protection (ROVPTOV) main settings
Parameter
Start value
Operate delay time
Table 44. Arc protection (ARCSARC)
Characteristic
Operation accuracy
Operate time
Reset ratio
Table 45. Arc protection (ARCSARC) main settings
Parameter
Phase start value
(Operating phase current)
Ground start value
(Operating residual current)
Operation mode
Table 46. Multipurpose protection (MAPGAPC)
Characteristic
Operation accuracy
Table 47. Multipurpose analog protection (MAPGAPC) main settings
Parameter
Start value
Operate delay time
Operation mode
Function
Value (Range)
ROVPTOV
0.010...1.000 x U
ROVPTOV
40...300000 ms
Value
±3% of the set value or ±0.01 x I
Minimum
Operation mode = "Light
9 ms
only"
Reset time
Typical 0.96
Function
Value (Range)
ARCSARC
0.50...40.00 x I
ARCSARC
0.05...8.00 x I
ARCSARC
2=Light only
3=BI controlled
Value
±1.0% of the set value or ±20 ms
Function
Value (Range)
MAPGAPC
-10000.0...10000.0
MAPGAPC
0...200000 ms
MAPGAPC
Over
Under
1MRS757058 D
Step
0.001
n
1
n
Typical
Maximum
10 ms
12 ms
< 40 ms
Step
0.01
n
0.01
n
Step
0.1
100
-
33