80070608-1409ffff • 80070608-140affff
23.
2. If local, pull out the Operator Information Panel, observe and make note of what is being displayed on the
Checkpoint display for support reference.
24.
3. Using the IMM web interface, capture a 'Service Data' file (note:) for support reference.
25.
4. (Trained service technician only) Replace the CPU board, I/O board assembly and memory card identified.
26.
[FPGA version 5.02]
2. If local, pull out the Operator Information Panel, observe and make note of what is being displayed on the
27.
Checkpoint display for support reference.
3. Using the IMM web interface, capture a 'Service Data' file for support reference.
28.
4. Remove AC power.
29.
30.
5. Remove memory card identified and check for connector pin damage on memory card and CPU memory
card slot.
31.
a) Replace affected commodity if damage is found.
32.
6. Swap the memory card in the slot identified, with a memory card from another slot with the same
configuration of DIMMs (size, type, number)
33.
7. Restart the server and see if problem still identifies the same memory card slot.
34.
a) If problem remains with original slot, replace the I/O board assembly.
35.
b) If problem occurs in slot where original memory card was moved to, replace the memory card.
80070608-1409ffff Sensor [SensorElementName] has transitioned to non-recoverable.
Explanation: A fault has occurred on a memory card.
May also be shown as 800706081409ffff or 0x800706081409ffff
Severity: Error
Alert Category: Critical
Serviceable: No
CIM Information: Prefix: PLAT and ID: 0530
SNMP Trap ID: 4
Automatically notify Support: No
User response: Replace any memory card that is indicated by a lit error LED.
80070608-140affff Sensor [SensorElementName] has transitioned to non-recoverable.
Explanation: A CPU VRD failure has occurre.
May also be shown as 80070608140affff or 0x80070608140affff
Severity: Error
Alert Category: Critical
Serviceable: No
CIM Information: Prefix: PLAT and ID: 0530
SNMP Trap ID: 4
Automatically notify Support: No
User response:
1.
Critical: Do Not attempt to power the system on, or AC cycle.
2.
1. If local, pull out the Operator Information Panel, observe and make note of what is being displayed on the
Checkpoint display for support reference.
3.
2. Using the IMM web interface, capture a 'Service Data' file (note:) for support reference.
4.
3. If the Checkpoint display repeatedly blinks F:A then 6:8.
- (Trained service technician only) Replace the CPU board
5.
422
IBM System x3850 X5 and x3950 X5 Types 7145, 7146, 7143, and 7191: Problem Determination and Service Guide