806f010c-18810014 • 806f010c-18810015
806f010c-18810014 Uncorrectable error detected for [PhysicalMemoryElementName] on Subsystem
[MemoryElementName].
Explanation: A memory uncorrectable error has occured in DIMM 20 of memory expansion unit(MEU).
May also be shown as 806f010c18810014 or 0x806f010c18810014
Severity: Error
Alert Category: Critical
Serviceable: No
CIM Information: Prefix: PLAT and ID: 0138
SNMP Trap ID: 41
Automatically notify Support: No
User response:
1. Refer to TIP H212293 for minimum code level.
2. Check the IBM support site for any applicable retain tip or firmware update that applies to this memory error.
3. Swap the affected DIMM with a similar DIMM (size/type) on a different channel.
4. Re-enable all DIMM slots.
5. If the failure remains on the original slot, replace the DIMM that was not moved. If the failure follows the DIMM
that was moved, replace the DIMM that was swapped.
6. If the problem re-occurs with the same DIMM connector, inspect DIMM connector for foreign material. If
damaged, replace the MEU board.
806f010c-18810015 Uncorrectable error detected for [PhysicalMemoryElementName] on Subsystem
[MemoryElementName].
Explanation: A memory uncorrectable error has occured in DIMM 21 of memory expansion unit(MEU).
May also be shown as 806f010c18810015 or 0x806f010c18810015
Severity: Error
Alert Category: Critical
Serviceable: No
CIM Information: Prefix: PLAT and ID: 0138
SNMP Trap ID: 41
Automatically notify Support: No
User response:
1. Refer to TIP H212293 for minimum code level.
2. Check the IBM support site for any applicable retain tip or firmware update that applies to this memory error.
3. Swap the affected DIMM with a similar DIMM (size/type) on a different channel.
4. Re-enable all DIMM slots.
5. If the failure remains on the original slot, replace the DIMM that was not moved. If the failure follows the DIMM
that was moved, replace the DIMM that was swapped.
6. If the problem re-occurs with the same DIMM connector, inspect DIMM connector for foreign material. If
damaged, replace the MEU board.