Onboard PLC parameters

The following parameters are associated with the Onboard PLC
program.
11.47
Drive Onboard PLC program enable
RW
Uni
0 to 2
This parameter is used to start and stop the drive Onboard PLC program.
Value
0
Halt the drive Onboard PLC program.
Run the drive Onboard PLC program (if installed). Any out-of-
range parameter writes attempted will be clipped to the
1
maximum / minimum values valid for that parameter before
being written.
Run the drive Onboard PLC program (if installed). Any out-of-
2
range parameter writes attempted will cause a 'UP ovr' trip.
11.48
Drive Onboard PLC program status
RO
Bi
-128 to +127
The drive Onboard PLC program status parameter indicates to the user
the actual state of the drive Onboard PLC program.
Value
Onboard PLC program caused a drive trip due to an error
-n
condition while running rung n. Note that the rung number is
shown on the display as a negative number.
0
Onboard PLC program is not installed.
1
Onboard PLC program is installed but stopped.
2
Onboard PLC program is installed and running.
When an Onboard PLC program is installed and running, the lower
display of the drive flashes 'PLC' once every 10s.
11.49
Drive Onboard PLC programming events
RO
Uni
0 to 65,535
The drive Onboard PLC programming events parameter holds the
number of times an Onboard PLC program download has taken place
and is 0 on dispatch from the factory. The Digitax ST is rated for one
hundred ladder program downloads. This parameter is not altered when
defaults are loaded.
11.50
Drive Onboard PLC program maximum scan time
RO
Uni
0 to 65,535 ms
The Onboard PLC program maximum scan time parameter gives the
longest scan time within the last ten scans of the drive Onboard PLC
program. If the scan time is greater than the maximum value which can
be represented by this parameter, the value will be clipped to the
maximum value.
11.51
Drive Onboard PLC program first run
RO
Bit
OFF (0) or On (1)
78
Electrical
Getting
Basic
installation
started
parameters
US
2
Description
NC
PT
Description
NC
PT
NC
PT
NC
PT
www.controltechniques.com
Running the
SMARTCARD
Optimization
motor
Operation
The Drive Onboard PLC program first run parameter is set for the
duration of program scan from the stopped state. This enables the user
to perform any required initialisation every time the program is run. This
parameter is set every time the program is stopped.
10.6

Onboard PLC trips

The following trips are associated with the Onboard PLC program.
Trip
Onboard PLC program: Cannot access Onboard
UP ACC
PLC program file on drive
Disable drive - write access is not allowed when the
drive is enabled.
98
Another source is already accessing Onboard PLC
program - retry once the other action is complete.
UP div0
Onboard PLC program attempted divide by zero
90
Check program
Onboard PLC program variables and function
UP OFL
block calls using more than the allowed RAM
space (stack overflow)
95
Check program
Onboard PLC program attempted out of range
UP ovr
parameter write
94
Check program
Onboard PLC program attempted access to a non-
UP PAr
existent parameter
91
Check program
Onboard PLC program attempted write to a read-
UP ro
only parameter
92
Check program
Onboard PLC program attempted read of a write-
UP So
only parameter
93
Check program
UP udF
Onboard PLC program undefined trip
97
Check program
UP uSEr
Onboard PLC program requested a trip
PS
96
Check program
10.7

Onboard PLC and the SMARTCARD

The Onboard PLC program in a drive may be transferred from the drive
to a SMARTCARD and vice versa.
To transfer an Onboard PLC program from the drive to a
SMARTCARD, set Pr xx.00 to 5yyy and reset the drive
To transfer an Onboard PLC program from the SMARTCARD to a
drive, set Pr xx.00 to 6yyy and reset the drive.
(Where yyy is the data block location, see Table 9-1 SMARTCARD data
blocks on page 71 for restrictions on block numbers).
If an attempt is made to transfer an Onboard PLC program from a drive
to the SMARTCARD when the drive contains no program, the block is
still created on the SMARTCARD but it will contain no data. If this data
block is then transferred to a drive, the destination drive will then have
no Onboard PLC program.
The smallest SMARTCARD compatible with Digitax ST has a capacity of
4064 bytes and each block can be up to 4064 bytes in size. The
maximum size of a user program is 4032 bytes so it is guaranteed that
any Onboard PLC program downloaded to a Digitax ST will fit on to an
empty SMARTCARD. A SMARTCARD can contain a number of
Onboard PLC programs until the capacity of the card is used.
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
Data
Diagnosis
Digitax ST User Guide