Weigand Reader Wiring Diagram - Ness D8xD Installer Manual

Deluxe alarm control panel
Table of Contents

Advertisement

ACCess Control
WIRING A SINGle ReADeR
P301e 1e is OFF (Reader addresses not used)
Connect only 1 reader.
In this mode the panel is compatible with the 101-091 Ness
IDTeck Fingerprint Reader or the 101-014 Ness Ultraprox
Weigand Reader.
Recommended cable is twisted 3 pair
shielded cable with only one end of the
shield connected to ground.
For cable runs exceeding 75m use the Ness
Weigand data repeater.
Grn
Wht
Red
Blk
Violet
not used
101-014
Ultraprox
VIOLET WIRE sets
Weigand
Reader
the reader number.
If P301E 1E is off,
this wire is not used.
ck
FGR006
rprint
d output.
reQUest to exit (rex) Using A keyPAD CoDe
Codes selected for Code Only Arming can be used as ReX codes for access control functions. That is, the code can
operate an output instead of arming/disarming the panel.
There are two conditions needed to make the code operate as a ReX code - It is assigned to CODe ONly ARM and it
is not assigned to either Area 1 or Area 2.
The first digit of the user code determines which AUX output is operated by the ReX code. That is, a ReX code in the
format 1xxx operates AUX1, 2xxx operates AUX2 and 3xxx operates AUX3.
Notes:
1. Reader 1 can also use codes starting with 4-9 if only one exit point is used.
2. Set P318e, P328e, P338e options to select appropriate AUX outputs.
3. Set corresponding P121e, P122e, P123e, P124e options to 8e.
setup example:
• User Codes 1555, 2555, 3555 are programmed to be Code Only Arm and are not assigned to Area 1 or Area 2.
• P318E 1E, P328 2E, P338 3E are programmed to set reader output to selected Aux output.
• P121E 8E, P122E 8E, P123E 8E are programmed to set AUX outputs to reader.
operation example:
• Code 1555 activates door associated with AUX1 (READER 1).
• Code 2555 activates door associated with AUX2 (READER 2).
• Code 3555 activates door associated with AUX3 (READER 3).
82
Connect to READER header
on the panel main board.
Blu
Blu
Brn
Brn
Grn
Grn
Wht
Wht
Red
Red
Blk
Blk
Optional Reader Interface board.
Part No. 106-012
NeSS D8X / D16X DelUXe CONTROl PANel – INSTAllATION MANUAl
WIRING MUlTIPle ReADeRS
P301e 1e is ON (Use Reader addresses)
When multiple readers are used, the panel needs to
identify the individual readers.
The 101-014 Ness Ultraprox Weigand Readers can be
addressed as Reader 1, 2 or 3 by connecting the Violet
wire to an appropriate terminal.
If using multiple Weigand readers, they must be either All
addressable or All non-addressable.
That is, use either three Ness 101-014 addressable Weigand
readers or three generic Weigand readers.