Ness D8 Installation & Programming Manual

Ness D8 Installation & Programming Manual

Control panel and dialer
Hide thumbs Also See for D8:
Table of Contents

Advertisement

N E S S D 8
C O N T R O L P A N E L A N D D I A L L E R
INSTALLATION & PROGRAMMING MANUAL
NESS D8 CONTROL PANEL V4 – INSTALLATION MANUAL, REVISION 1
A$12.00 INC GST
VERSIONS COMMENCING NOVEMBER 2001

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the D8 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Ness D8

  • Page 1 C O N T R O L P A N E L A N D D I A L L E R INSTALLATION & PROGRAMMING MANUAL NESS D8 CONTROL PANEL V4 – INSTALLATION MANUAL, REVISION 1 A$12.00 INC GST VERSIONS COMMENCING NOVEMBER 2001...
  • Page 2 Document Part Number: 890–265 TELECOMMUNICATIONS COMPLIANCE For product: 100–191 D8 LED Control Panel (V4) 100–688 D8 LCD Control Panel (V4) © 2001 Ness Security Products Pty Ltd ACN 069 984 372 D8 V4 installer rev1 pmo221001 Specifications may change without notice.
  • Page 3: Table Of Contents

    RADIO OPTIONS Misc. options 1 ............. 34–35 Radio Quick Start ............54 Misc. options 2 ............. 36–37 Ness Radio Interface ..........54 Signal strength meter ..........54 DIALLER OPTIONS Radio Devices, Operation .......... 55 Telephone Numbers 1 & 2 ......... 38 Radio Supervision, Defined ........
  • Page 4: Introduction

    Any combination of hardwire or Company to ISO 9001. radio zones • Full radio supervision This version of the D8 introduces a number of new features including Radio PIR • Contact ID Dialler Format Supervision, Ness LCD Keypad and numerous other innovations. •...
  • Page 5: Specifications

    Remote Keypad input ..Proprietary Zone list label Maximum Keypads ..... 3 Housing cover screws J2 Header ......Multi-pin connector for the Ness Radio Interface (100-200) Circuit board standoff OUTPUTS Siren ........On board siren driver. Timed output. Maximum 3 x 8 Ohm horn speakers Strobe .........
  • Page 6: Connection Diagram

    Ness 17V AC Plug Pack (840-029) (Australia only) EARTH (White) EARTH HEATSINK ZONE CONNECTION EXAMPLES N.C. Normally Closed Devices NESS D8 N.C. Contacts Zone N.O. Normally Open Devices NESS D8 N.O. Contacts Zone NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 7: Wiring Examples

    SIREN output SIREN in parallel with the Horn Speaker/s. STROBE LIGHT TIP: (NOI300) 100-171 Internal Horn Speaker has WHITE wires. 100-172 Internal Siren has RED & BLACK wires. NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 8 24hr input. AC INPUT TERMINALS These terminals are for the connection of the Ness plugpack. The Ness D8 requires an AC transformer rating of 1.4 Amps @ 17 V AC minimum. (Ness Part No. POW215) BATTERY These terminals are for the connection of a sealed lead-acid rechargeable 12Volt battery.
  • Page 9 SIREN, and RESET outputs and 200mA from the STR output. A maximum of 2 x 1 Watt Strobes (Ness Part No. NOI300) can be connected to Recommended maximum power load: this output. The output is protected by an Automatic Reset fuse.
  • Page 10: Keypad

    Phone line fault or LINE Normal Dialler is on line failure to communicate PROGRAM Normal User Program Mode Installer Program Mode Not Ready Ready to Arm Not ready to Arm NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 11: Operation Summary

    ALARM MEMORY ENTER or... [User Code] Press repeatedly to display the last MEMORY Press repeatedly to display 30 events the last 30 events ENTER To exit Memory mode To exit Memory mode NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 12: Quick Start Programming

    P R O G R A M M I N G QUICK START PROGRAMMING Use one of these programming summaries for fast setup of your D8 as a Local, Audible Monitored or Central Station Monitored system. The control panel will be ready for use immediately.
  • Page 13: How To Enter Program Mode

    This is Operating Mode (PROGRAM light is OFF). Selects a program The current value Enter new KEY SEQUENCE option (address) is displayed data IN PROGRAM MODE The keypad lights or icons will display the current value NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 14: User Codes

    Radio Key programming, User Code 11 P21E P10E User Code 12 P22E Page 57 User Code 13 P23E User Code 14 P24E User Code 15 P25E Installer Code P99E Installer Code 000000 NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 15: Timers

    • Programmable from 1 – 99 minutes EXAMPLE: To program Siren Time to be 4 minutes: • Siren times of longer than 5 minutes are P29E 4E contrary to noise pollution regulations in most areas. NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 16: Vibration Sensitivity

    The bracket must always be mounted horizontally and the arrow must point N/C Vibration BLUE contacts up for any required setting. N/C Tamper YELLOW 20mm GREEN loop 350mm cable 36mm 3mm holes at 27mm spacing NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 17: Zone Assignment

    Entry beeps can be disabled by program option P60E 1E. • When a zone is selected for this type, it is automatically deselected from any other zone type in the DELAY GROUP NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 18: Area Partitioning

    P44E [Zone No]E ON: The zone is a Lockout zone • RELATED OPTIONS: P60E 4E Tamper Reset Lockout P45E, P46E AREA PARTITIONING See page 20 P47E – P50E ASSIGNING USER CODES TO AREAS See page 21 NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 19 P53E [Zone No]E ON: The zone is a Day zone Instant alert when a delivery door is opened. Doorway alert for a shop. Turn ON option P63E 7E for keypad sonalert when a Day zone alarms. NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 20 P46E use the [Zone No] E sequence to turn ON zone 1 and zones 5~8. P45E: AREA 1 zones P46E: AREA 2 zones Example: Zone 1 is assigned to both Areas, so it is a Common Zone NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 21 • For this option [Zone No] E toggles the selection ON and OFF. EXAMPLE: AREA 2 User codes 9–15 are assigned to AREA 2. P49E User Codes 1-8 P50E User Codes 9-15 NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 22: Zone To Output Mapping

    P56E [Zone No]E OFF: The zone will not trigger the Keypad Sonalert NOTES: P56E [Zone No]E ON: The zone will trigger the Keypad Sonalert • 0E will turn all selections OFF MEMORY E will turn all selections ON NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 23 P59E [Zone No]E OFF: The zone will not trigger the AUX2 output • 0E will turn all selections OFF P59E [Zone No]E ON: The zone will trigger the AUX2 output MEMORY E will turn all selections ON NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 24: Various Options

    An externally fitted, normally open momentary Keyswitch can be used to Arm, PROGRAM MODE LEVEL: Disarm or change the D8 to Monitor mode. Installer, Remote by PC The keyswitch is wired to zone 8 (zone 8 is then no longer available as a...
  • Page 25 P60E 8E toggles the option ON and OFF P60E 8E OFF: ARM1 & ARM2 outputs turn on instantly P60E 8E ON: ARM1 & ARM2 outputs turn on at end of Exit Time NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 26: Tamper/Keypad Panic Output Mapping

    P61E 7E: Keypad Panic Alarm to Keypad Sonalert output the PANIC keys on the keypad (* E or ** P61E 8E: Keypad Panic Alarm to Siren output together, depending on Option P64E6E). NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 27: System Operation Shortcuts

    P62E 8E ON: Exit Time is multiplied by 10 • RELATED OPTIONS: P28E Exit Time EXAMPLE: If P28E = 22 seconds then if P62E 8E is ON, the exit time is 22 x 10 = 220 seconds. NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 28: Monitor Mode Output Mapping

    Options P63E 1E–8E allow different outputs to be triggered when the panel is in MONITOR and DAY modes. For ZONE TO OUTPUT MAPPING (Armed & 24hr states) – see Options P54E – P59E, page 22 NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 29: Miscellaneous Options

    P64E 4E toggles the option ON and OFF • RELATED OPTIONS: P68E 8E Quiet Chirps P64E 4E OFF: No Arm/Disarm chirps P64E 4E ON: Siren & Strobe outputs will chirp on arm/disarm NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 30 PROGRAMMING SEQUENCE: OFF: No Keypad Medical Alarm P64E 8E toggles the option ON and OFF NOTES: P64E 8E OFF: No Keypad Medical Alarm • RELATED OPTIONS: P64E 8E ON: Keypad Medical Alarm enabled NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 31: Supervised Radio Zones

    SUPERVISION TIME The SUPERVISION TIME is the time allowed between radio transmissions PROGRAM MODE LEVEL: received by the D8 from any Supervised Ness Radio PIR (100–663). Installer, Remote by PC The SUPERVISION TIME setting is from 01 to 24 hours.
  • Page 32 P66E 3E OFF: Supervision Keypad Sonalert disabled P65E Supervised Radio Zones AND all Supervision outputs trigger instantly P66E 3E ON: Supervision Keypad Sonalert enabled AND all Supervision outputs are delayed by 1 minute NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 33 NOTE: If both P66E 7E and 8E are both ON then the Supervision time is sped up by 60. For instance if P67E is set to 1 hour (60 minutes), then this option will reduce it to 1 minute. (i.e., 60 divided by 60). NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 34: Misc. Options 1

    • If P68E 3E and 4E are both selected ON, then 4E has priority. P68E 4E OFF: Radio Key Panic triggers control panel Panic P68E 4E ON: Radio Key Panic pulses AUX1 NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 35 P68E 7E 4th BUTTON RADIO KEY FOR AUX1 Ness 4 Button Radio Key only – this option changes P68E 3E and 4E to work PROGRAM MODE LEVEL: with the 4th Button of a 4 Button Radio Key instead of the PANIC button.
  • Page 36: Misc. Options 2

    P69E 3E toggles the option ON and OFF • This does not affect the RESET output P69E 3E OFF: Normal siren sound in Monitor Mode P69E 3E ON: Quiet Siren sound in Monitor Mode NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 37 P R O G R A M M I N G P69E 4E 6 BEEPS ON ARMING Normally the keypad/s onboard SONALERT gives 3 beeps when the D8 is PROGRAM MODE LEVEL: Armed. Turning this option ON will give 6 keypad beeps when Arming.
  • Page 38: Telephone Numbers 1 & 2

    0000 P70E, P71E TELEPHONE NUMBERS 1 & 2 The D8 can dial up to 2 phone numbers when an event is to be transmitted to a PROGRAM MODE LEVEL: remote location. Telephone numbers may be up to 15 digits long.
  • Page 39: Telephone Number 3 - Test Calls

    P86E 3E Audible DTMF format EXAMPLE: To program Telephone No.4 to be 02 8825 1234: P86E 4E Audible Pulse format P70E0288251234E P86E 5E Contact ID + Audible DTMF P86E 6E Contact ID + Audible Pulse NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 40: Report Zone Alarms

    All zones report Restorals P79E [Zone No]E toggles the option ON and OFF NOTES: P79E 1E–8E OFF: Multiple Zone Alarms disabled for that zone P79E 1E–8E ON: Multiple Zone Alarms enabled for that zone NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 41: Report Miscellaneous Alarms

    • RELATED OPTIONS: P76E Report zone restorals P82E 1E: Send Restoral immediately P82E 2E: Send Restoral after siren time P82E 3E: Send Restoral on Disarm & seal P82E 4E: Send Restoral on Disarm always NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 42: Test Call Interval

    P85E 1E–3E turns the option ON • Only one option is allowed to be ON P85E 1E: Auto Dialling (PULSE or DTMF) P85E 2E: Pulse Dialling always P85E 3E: DTMF Dialling always NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 43: Disable Dialler

    • Only one option in the range P86E 4E turns the option ON P86E 1E—6E is allowed to be ON • This is the best option to select for P86E 4E ON: Audible PULSE format enabled Audible Monitoring. NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 44: Contact Id Reporting Codes

    – Event checksum Mains Fail AAAA Panel Battery Fail AAAA Open AAAA by User Close AAAA by User Cancel AAAA by User Zones 1~8 Manual Exclude AAAA 001-008 Zones Auto Exclude AAAA 001-008 NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 45: Alternate Dialling

    2 attempts per telephone number. • RELATED OPTIONS: P87E 1E Alternate dialling PROGRAMMING SEQUENCE: P87E 4E toggles the option ON and OFF P77E 4E OFF: Maximum 10 dialling attempts P87E 4E ON: Maximum 4 dialling attempts NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 46: Area1 Open/Close Reports

    P88E 4E toggles the option ON and OFF NOTES: P88E 4E OFF: No Strobe Flash on kiss-off • RELATED OPTIONS: P88E 4E ON: Strobe Flash on kiss-off enabled P88E 3E Siren Chirp on kiss-off NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 47: Forced Opening Report

    ON: Auto Exclude Reports enabled P88E 8E toggles the option ON and OFF NOTES: P88E 8E OFF: No Auto Exclude Reports • P88E 8E ON: Auto Exclude Reports enabled P88E 7E Manual Exclude Reports NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 48: Enable Test Calls

    To turn Listen-In off, go back into Installer Program mode and toggle the option temporarily connect a spare horn OFF. speaker to the Siren output. PROGRAMMING SEQUENCE: P89E 3E toggles the option ON and OFF P89E 3E OFF: No Listen-In P89E 3E ON: Listen-In enabled NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 49: Swinger Shutdown

    P89E 6E toggles the option ON and OFF NOTES: P89E 6E OFF: No Line Fault output • RELATED OPTIONS: P89E 6E ON: Line Fault to AUX2 enabled P89E 5E Line Fault Monitor NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 50: Remote Access

    P90E 1E ON: Remote Access enabled P90E 2E DIRECT CONNECT This allows a direct connection to be used between the D8 telephone output PROGRAM MODE LEVEL: and an on site computer with modem. A special NESS adapter is required Installer, Remote by PC when using this connection.
  • Page 51: Remote Disarming/Aux Control/Status Reporting

    Callback using Telephone Number 4. P90E 1E Enable Upload/Download P81E Telephone Number 4, Callback PROGRAMMING SEQUENCE: P90E 8E toggles the option ON and OFF P90E 8E OFF: No Callback P90E 8E ON: Callback Mode enabled NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 52: Remote Access Options

    This function resets the microprocessor. The effect is the same as powering down and PROGRAM MODE LEVEL: powering up again. Installer, User Program Mode PROGRAMMING SEQUENCE: FACTORY DEFAULT: P88888888E (eight 8’s) Panel Reset [not applicable] NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 53: Clear Radio Devices

    Installer, Remote by PC code is 000000. FACTORY DEFAULT: PROGRAMMING SEQUENCE: 000000 P99E [Enter new code]E [Enter new code again]E NOTES: (Unlike User Codes, the installer code is not displayed when programming) NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 54: Radio Quick Start

    • In cases where radio reception needs to be improved, the Radio Interface can be If the Ness Radio Interface is correctly installed, the D8 keypad will flash the RADIO light ON installed up to 50 metres away from the when any radio signal is detected (from both programmed and non-programmed radio control panel.
  • Page 55: Radio Devices, Operation

    SUPERVISION RADIO DEVICES – OPERATION ALARM: Any Ness Radio Device can operate on any zone 1–8 as programmed by P01E~P08E. The hardwired zones 1–8 continue to operate in parallel. Radio Keys can also operate on radio zones 1~8 for special purposes, but they should normally be used as Radio Codes.
  • Page 56: Radio Device Programming

    N E S S R A D I O P01E ~ P08E RADIO DEVICE PROGRAMMING Each of the 8 zones of the D8 can be a radio zone. Once programmed, zones PROGRAM MODE LEVEL: can accept both Radio Devices and normal zone inputs simultaneously.
  • Page 57: Radio Key Programming

    Each of the 15 User Codes, except for the Master Code, can be programmed to PROGRAM MODE LEVEL: be Radio Codes. This allows up to 14 Ness Radio Keys to be used for Arming Installer, Remote by PC and Disarming of the panel. The optional 100–200 Ness Radio Interface is FACTORY DEFAULT: required for Radio Keys to operate.
  • Page 58: Audible Monitoring Operation

    CENTRAL STATION MONITORING The D8 control panel has an on-board digital dialler which can send detailed CENTRAL STATION MONITORING alarm messages to a Central Monitoring Station. The digital messages can include information about the zone/s which caused the alarm, tamper alarms, low battery or mains failure reports, and it can also...
  • Page 59: Remote Operation By Telephone

    OPERATING THE D8 BY TELEPHONE The D8 will allow a user to call in to SEQUENCE OF OPERATION. AUDIBLE FEEDBACK the panel, using a standard DTMF 1. Phone the D8 telephone number 3 BEEPS: telephone, and remotely Arm or and listen for the required •...
  • Page 60: Ness Accessories

    2.4 metre ceiling height. PET AWARE DETECTORS The Ness Quantum™ Pet Aware PIR and Pet Aware DUAL are able to discriminate between household pets and unwanted human intruders, allowing you to secure your home with your pets indoors.
  • Page 61: Wireless Products

    Also operates Monitor mode and Panic when used with the Ness D16, D24 panels. The Ness radio Keypad is suitable for use as a portable keypad or for adding an extra keypad in areas where it is not possible to install wires.
  • Page 62: Programming Options Summary

    These options are available in User Program Mode. 8E Exit Time x 10 P81E Telephone No.4 for Callback none ALL options are available in Installer Program Mode D8 (V4) Options Summary © 2001 Ness Security Products NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 63: Installation Record

    User Code 9 P19E User Code 10 P20E User Code 11 P21E User Code 12 P22E User Code 13 P23E User Code 14 P24E User Code 15 P25E © 2001 Ness Security Products NESS D8 (V4) CONTROL PANEL – INSTALLER MANUAL...
  • Page 64 blank...