ACCess Control
P300e
ProgrAm moDe leVel
Installer mode or NessComms.
RF Card
If connecting multiple readers, the
option to enable multiple readers
(P301e 1e) should be turned on
before programming any access cards.
(enabling P301e 1e erases existing card
programming).
If P301e 3e is enabled, a
momentary push button can be
wired to zone 8 as shown.
For example, this option allows the reader
output to operate a door lock during the
day by presenting your card. Then at the
end of the day press the push button
within 5 seconds of presenting the card
and the panel will arm.
NORMALLY OPEN
Zone 8 Input
Momentary pushbutton
Z8
C
NORMALLY CLOSED
Zone 8 Input
Momentary pushbutton
Z8
C
76
Option No.
Description
P300e
DeFAUlT All ACCeSS CONTROl OPTIONS
DeFAUlt All ACCess Control oPtions
enter P300e in Installer program mode to return all access control programs to
factory default values.

PROGRAMMING ACCeSS CARDS

If the panel has 1, 2 or 3 Weigand proximity readers connected up to 55 of the panel's
user codes can be programmed as Reader Codes. This allows arming/disarming by
access card and operation of AUX outputs to open electric door strikes.
Use the extra Options programming mode to enable selected user codes to Readers
1, 2 or 3. When a user code is enabled as a Reader Code, its Keypad Code, (if any),
is automatically deleted. A user code enabled as a Reader Code cannot also be a
Keypad Code or Radio Code.
PROGRAMMING SeQUeNCe:
In Installer Program Mode, enter the option number for the user code to be
 
programmed. (P202e–P256e).
Press eXClUDe e to enter extra Options mode. (exclude light turns on).
Press 6e, 7e or 8e to assign the user code to Reader 1, 2 or 3. (Keypad
light 6, 7 or 8 will turn on).
Press eXClUDe e to exit extra Options mode. (exclude light turns off).
Press 1e
the keypad reaDY light will turn on to indicate that the user code is ready to accept an access card.
if a code is already programmed the reaDY light will not turn on and a warning beep will sound. to
clear the code, press 0e, then go back to step 5. (0e clears any existing codes).
Present a valid access card to the reader.
if the access card is of the correct type, the reader's orange light will turn on.
if the access card is accepted, the keypad reaDY light will turn off and 3 beeps will sound.
if the reaDY light stays on and a warning beep sounds, the access card is already assigned to another
user code and must be cleared from that user code first.
Once a card is programmed to a user code it can be used to:
ARM THe PANel.
To allow arming with a double read, enable option P301e 2e.
To allow arming with a single read and pushbutton, enable option P301e 3e.
(Both methods can be enabled at once).
DISARM THe PANel.
To allow disarming, (single read), enable option P301e 4e.
(This option can be enabled if necessary. A user may be allowed to arm by access
card but not disarm, or vice-versa).
OPeRATe AUX OUTPUT/S.
FOR eXAMPle TO OPeRATe DOORSTRIKe/S
To allow the operation of panel AUX outputs by access card, the reader to which
the card is assigned must be programmed to operate one of the four AUX outputs.
• First, enable one or more AUX outputs to be a Reader output, P121E 8E, P122E
8e, P123e 8e and P124e 8e.
• If using more than one 101-014 Ultraprox Reader, enable P301E 1E to Use
Reader Addresses.
• Next, assign which reader will trigger which AUX output. P318E - P338E
NeSS D8X / D16X DelUXe CONTROl PANel – INSTAllATION MANUAl