P r o g r A m m i n g
Only one of the P122e options may be selected.
Option No.
Description
P122e 1e
Zone alarms to Aux2
2e
Zone Supervision alarms to Aux2
3e
AutoTimer + R/Key Panic TOGGleS Aux2
4e
Radio Key AUX button Pulses Aux2
5e
Phone line fail to Aux2
6e
[not used]
7e
DOTl alerts to Aux2
8e
Reader output pulses Aux2
P122e 1e-8e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
1e on.
notes
Only one option can be on. Turning an
option on turns off another.
relAteD oPtions
P142e 1e-8e enhanced AUX2 options.
P354e 7e-8e AutoTimer1 AUX2 options.
P359e 7e-8e AutoTimer2 AUX2 options.
P364e 7e-8e AutoTimer3 AUX2 options.
P369e 7e-8e AutoTimer4 AUX2 options.
P122e 1e
relAteD oPtions
P59e Aux2 zones.
P122e 2e
relAteD oPtions
P65e, P66e, P67e Radio Supervision.
P122e 3e
Available in D8x/D16x V6 and later.
relAteD oPtions
P350e to P369e. AutoTimers 1 to 4.
P122e 4e
relAteD oPtions
P146e AUX2 Timer
P122e 5e
P122e 7e
relAteD oPtions
P303e DOTl zones.
P304e DOTl timer.
P122e 8e
relAteD oPtions
P318e, P328e, P338e, P319e, P329e,
P339e.
60

AUx2 OUTPUT OPTIONS

Default
OFF
OFF
OFF
OFF
OFF
OFF
OFF
AUx2 oUtPUt oPtions
P122e is one of several options which control the behaviour of the AUX2 output.
One of the most powerful features of the D8x/D16x panels is the flexibility to control
the AUX outputs by various events and alarms. If the AUX2 output does not behave as
expected, please check all related options such as AutoTimers and P142e options.
TO PROGRAM
1. Press P122e.
2. Press 1e ... 8e to turn an option on. Only one option can be on.
Zone AlArms to AUx2
With this option ON, zones selected in P59e will turn on Aux2 when they go into alarm. The
Aux2 output turns off when the panel is disarmed/reset.
Zone sUPerVision AlArms to AUx2
Setting this option turns the AUX2 output ON when a SUPeRVISeD RADIO alarm is
triggered. The Aux2 output turns off when the panel is disarmed/reset.
enAble AUx2 For AUtotimer / rADio key AUx toggles AUx2
Dual action programming option.
When this option is on, AUX2 is enabled for use by AutoTimer and Radio Key/s AUX button
will TOGGle the AUX2 output.
rADio key AUx bUtton PUlse AUx2
When this option is on, Radio Key/s AUX button button will PUlSe the Aux2 output.
telePHone line FAUlt to AUx2
When this option is enabled, a telephone line fault condition will turn on the Aux2 output.
Aux 2 will turn off when the telephone line is restored.
Door oPen too long (Dotl) Alerts to AUx2
This option enables DOTl zones (P303e) to turn on AUX2 when the DOTl Time (P304e)
expires.
reADer oUtPUt to AUx2
This option enables an access control reader to pulse Aux2 when a valid access card is
presented. Set the reader using P318e, P328e or P338e.
NeSS D8X / D16X DelUXe CONTROl PANel – INSTAllATION MANUAl
Any or all of the P142e options may be selected.
Option No.
Description
P142e 1e
Area1 Armed to AUX2
ON
2e
Area2 Armed to AUX2
3e
Home Mode arm to AUX2
4e
Keypad toggle AUX2
5e
Telephone remote control of AUX2
6e
[not used]
7e
[not used]
8e
Pulse AUX2
Default
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF