Navigator, Saturn or KPX+ keypad options D8xCEL / D16xCEL ALArm ControL PAnEL 8 / 16 Zone Control Panels with Cellular Dialler 8 or 16 Various Cellular Operation by Operation and Access Powerful Auto-Time 8 x AUX Hardwired or Keypad Dialler...
Page 2
Ness. Ness reserves the right to make changes to features and specifications at any time without prior notification in the interest of ongoing product development and improvement.
• New modem chip allows common modems to be used for upload/download in 300baud mode. • All programming data is permanently stored in a non-volatile memory. • All inputs and outputs are heavily protected against lightning and high voltage supply transients. • High efficiency DC power supply with dual 17VAC/20VDC power input • Optional output expander. DIALLER • 3G dialler onboard • Direct-connect upload/download using NessComms™ software. • View system status and arm/disarm using NessComms™. • Remote control of outputs via telephone with voice prompts. • Operation via SMS messaging • Programming via SMS • Alarm reports via SMS or back-to-base • Remote operation and programming via the free NessXCEL app NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Direct connect via serial port for fast and easy programming • C-Bus Trigger Control and Enable Control. by laptop/PC. The Ness 450-xxx Serial Cable is required. • C-Bus events can control the D8x/D16x. • Multiple onboard SERIAL repeater ports means the D8x/ D16x panel can also connect to other serial devices while connected to MiniCENTRAL. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Backup battery position. switch. Connect to Suits up to 12V 7Ah battery. INTERNAL TAMPER pins. 3G SIGNAL LED LED on steady = Connecting to network LED Flashing= Valid SIM card installed NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
TAMP input. operation, until the panel is reset). PoWEr inPUt tErminALs A maximum of 2 x 1 Watt Strobes (Ness Part No. NOI300) can be These terminals are for the connection of the external power supply. connected to this output.
If required, this control panel can alternatively be This power supply has positive and negative 20VDC powered by a 17VAC (1.4A) plug pack. output however the polarity is not important in this case. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Wired Zone Supervision alarm (Zone number is indicated by zone lights) * The onboard clock is automatically updated from your cellular network. you should only need to adjust clock settings if the panel is being used 'offline' without a SIM card. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 11
Note that some Saturn keypad models do not have CELLULAR signal and real time clock display. Operational functions are unaffected, however it's recommended that at least one KPX+ keypad be installed to provide cellular signal indication. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Zone names can be customised by SMS. The Zone List display will show 8 zones for D8XCEL and 16 zones for D16XCEL. Touch to close the window. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
[UserCode]E[AuxNumber]E keypad. See P141E 4E, P142E 4E, P143E 4E, P144E 4E. Note, via SMS enter the Aux output numbers as double digits. For example to turn on Aux1 send [UserCode] E11E (therefore Aux2 is 22, Aux3 is 33 etc.) More information next page. * If a user code is assigned to a radio key and has Extra Option 4E enabled, (Code Only arming), then pressing OFF toggles the arm/disarm state. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
The PANIC alarm sounds the sirens and strobe if programmed. Related options for Fire and Medical P75E, P77E, P191E, P193E, P161E, P126E 2E 3E, P69E 1E Related options for Panic P61E 5E~8E NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
This function displays the panel software version when in program mode. Displayed in decimal format by the zone LEDs. Example, version V6.1 is displayed by flashing 6 followed by 1. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
E to ensure an op- tion is ON or OFF instead of toggled. Example: P39E1E toggles option 1. P39E1U sets ON option 1. P39E1Z sets OFF option 1. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
D8XCEL and D16XCEL control panels can be operated and programmed by SMS (TXT) messaging from any mobile phone. The NESS XCEL free app is also available for easy operation for users and fast programming by installers. This section covers programming by direct SMS messaging from a mobile phone if not using NESS XCEL app.
CEntrAL stAtion monitoring Ness D8XCEL and D16XCEL series control panels have an on-board 3G dialler for communicating alarm messages to a central monitoring station or to a smartphone by SMS messaging. The digital messages can include information about the zone/s which...
As with any sms message it is SMS MESSAGE EXPLAINER possible that sms monitoring reports may be delayed or fail NESS security report Identifies the message as a Ness alarm panel report. to be delivered. such failures MyPANEL are a function of the cellular identifies the premises.
- rEQUEst stAtUs REQUEST PANEL STATUS By SMS D8XCEL and D16XCEL panel status can be interrogated by SMS. Check the sealed/ unsealed status of zones, check miscellaneous alarm status and check if the system is armed, all by SMS messaging and reply.
- tExt oUtPUt CHANGING TEXT OUTPUT D8XCEL and D16XCEL have an extensive library of text descriptions used in SMS messaging, and also give the user the ability to customise the text output to suit individual needs. For example, the default text sent for a zone alarm is:...
SECURITy SySTEM ZONE 16 FAILURE SHORT ARM FIRE SIREN FIRE SIREN SOFT MONITOR from SOFT SIREN FROM SONALERT from PENDANT START HOME STROBE INSTALLER SUPERVISE INSTALLER ADDRESS 1 SUPERVISION FAILURE NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 23
DEViCE ProgrAmming sEE PAgEs 78-79 P101E – P116E UsEr CoDEs, ProgrAmming by kEyPAD P201E – P256E D8XCEL and D16XCEL have 56 User Codes which are used to operate the panel by a variety of methods. ProgrAm moDE LEVEL User, Installer...
REX codes. See page 86. P240E 5E RADIO CODE. Enables selected user codes as Radio Codes P241E for operation by Ness Radio Key or Radio Keypad. (Page 79 - P242E how to program Radio Codes). P243E 6E READER CODE 1.
P29E > Siren Reset Time > Enter new time E • Programmable from 1 – 99 minutes. P[MasterCode]E P[InstallerCode]E P29E [NewTime]E SMS* • Siren times of longer than 5 minutes are contrary to noise pollution Or use NessXCEL regulations in most areas. * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
(using a metal object such as a screwdriver blade) will cause an alarm. * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
P40E, P42E, P43E KPX+ PRO TIP When selecting zones, mEmory E selects all zones, 0 E deselects all zones * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 28
Common zones. P[MasterCode]E P[InstallerCode]E P46E [Zone Number]E • If no Area operation is required, Or use NessXCEL assign all zones to Area 1. (This is also the factory default). * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Zones. The selected zones are indicated by entering program mode. default beep warning tone. See P126E 4E. the corresponding zone number. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 30
P120e 6e Smart Beeps for Home and Or use NessXCEL Day zones. See page 29 for information about TEMPORARy DAy ZONES * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Or use NessXCEL KPX+ PRO TIP When selecting zones, mEmory E selects all zones, 0 E deselects all zones * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 32
P121e, P123e Day zone output mapping. KPX+ P59E [Zone Number] E to enable/disable zones P59E > Select zones NAVIGATOR SMS* P[MasterCode]E P[InstallerCode]E P59E [Zone Number] E Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
KEySWITCH of the global EOL resistor value set N/O contacts Optional PANIC BUTTON. by P129E N/C contacts in series. * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 34
P144E 1E, AUX4 on when Area1 arms. SMS* P[MasterCode]E P[InstallerCode]E P60E 8E P144E 2E, AUX4 on when Area2 arms. Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
• A Keypad Panic Alarm can be caused by the PANIC keys on the keypad (* E NAVIGATOR P61E > enable/disable 5E ~ 8E as required or ** together, depending on Option P[MasterCode]E P[InstallerCode]E P61E 5E ~ 8E as required SMS* P126E1E). Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
OFF: Exit Time x10 disabled. NAVIGATOR P62E > enable/disable 8E rELAtED oPtions P[MasterCode]E P[InstallerCode]E P62E 8E SMS* P28E Exit Time. Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
P51E Set Home zones. NAVIGATOR P64E > enable/disable 1E P63E 1E–4E Home Mode output P[MasterCode]E P[InstallerCode]E P64E 1E SMS* mapping Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
P69E 5E Home Mode arming by radio key. P120E 2E Siren Chirp on Home Arming by Radio * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
The purpose of Radio Supervision is to verify the correct operation of Ness Radio PIRs. The Supervision signal from the Radio PIR tells the panel that the device has not been removed from radio range and is in working order.
Page 40
OFF: Supervision Siren output disabled. NAVIGATOR P66E > enable/disable 4E rELAtED oPtions P65E Supervised Zones. SMS* P[MasterCode]E P[InstallerCode]E P66E 4E Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 41
Installer Program Mode and on Arm or Disarm. rELAtED oPtions P65E Supervised Zones. P66E 1E–4E Supervision Alerts. P66E 7E–8E Supervision Time Speed- * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
P68E 1E DoUbLE PrEss rADio PAniC ProgrAm moDE LEVEL Setting this option ON enables Double Press Panic for Ness Radio Keys, if fitted. The panel Installer will look for two radio Panic signals in a row to sound the Panic alarm.
Page 43
P120E 2E Home Arm chirps. P120E 3E Radio Key AUX / arms Home Or use NessXCEL Monitor P162E Chirp Siren Volume * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 44
The keypad beeps on Arm/Disarm P[MasterCode]E P[InstallerCode]E P69E 4E SMS* when Arming/Disarming by keypad, keyswitch or by Radio Key. Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 45
2. If another event causes a different keypad beep, the exit beeps resume once the event beeps are finished. * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Hex digits B, C, D, E, F * Key in the P72E option. ARM Key HOME Key EXCLUDE Key MEMORy key * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
DisPLAy for entering Pause, Star and Hash. PAUSE (1.6sec) ARM Key * (Star) HOME Key # (Hash) EXCLUDE Key * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
SMS messages (no alarm reports or ACK replies). See page 19 for SMS messaging examples. * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Or use NessXCEL KPX+ PRO TIP When selecting zones, mEmory E selects all zones, 0 E deselects all zones * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
P82E > enable/disable xE P76E Report zone restorals. P[MasterCode]E P[InstallerCode]E P82E xE SMS* Or use NessXCEL x = 1E, 2E, 3E or 4E * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Time Before Next Test Call and Or use NessXCEL the Real Time Clock into permanent memory. On power up these times will be restored. * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
The panel can send alarm reports to a central station by CID or to mobile phone number/s by SMS or both. * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
(up to the maximum number of calls). KPX+ P87E 4E to enable/disable the option NAVIGATOR P87E > enable/disable 4E P[MasterCode]E P[InstallerCode]E P87E 4E SMS* Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
KPX+ rELAtED oPtions NAVIGATOR P88E > enable/disable 4E P88E 3E Siren Chirp on kiss-off. P[MasterCode]E P[InstallerCode]E P88E 4E SMS* Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
ON: Auto Exclude Reports enabled. P88E > enable/disable 8E NAVIGATOR rELAtED oPtions P88E 7E Manual Exclude Reports. SMS* P[MasterCode]E P[InstallerCode]E P88E 8E Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
This option only applies to zones enabled to Report Multiple Zone Alarms. rELAtED oPtions P78E Report Multiple Zone Alarms. * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Or use NessXCEL KPX+ PRO TIP When selecting zones, mEmory E selects all zones, 0 E deselects all zones * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
000000. FACtory DEFAULt P99E [New Installer Code] E [New Installer Code] E KPX+ 000000 NAVIGATOR P99E > [New Installer Code] E [New Installer Code] E P[MasterCode]E P[InstallerCode]E P99E [New Installer Code] E SMS* Or use NessXCEL For a complete list of factory default values, see the Programming Options Summary on pages 87–92. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Zone 15 Battery Fail Zone 15 by P145E. Zone 16 Ext. Tamper Ext. Tamper Zone 16 Ext. Tamper Zone 16 * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 60
P119E > Select zones When selecting zones, MEMORy E P[MasterCode]E P[InstallerCode]E P119E [Zone Number] E selects all, 0 E deselects all. SMS* Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 61
AUx bUtton Arms homE moDE ProgrAm moDE LEVEL This option enables the AUX button on a Ness RK4 Radio Key to arm Home Mode. Installer When this option is enabled, options P122E 3E & 4E will be disabled, (AUX button to Aux2 FACtory DEFAULt options.
Page 62
NAVIGATOR P120E > enable/disable 8E rELAtED oPtions P60E 2E, 3E. P120E 1E, 4E, 5E P[MasterCode]E P[InstallerCode]E P120E 8E SMS* Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
This option enables an access control reader to pulse Aux1 when a valid access card is P318E, P328E, P338E, P319E, P329E, presented. Set the reader using P318E, P328E or P338E. P339E. * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Select 1 to 99 seconds. FACtory DEFAULt KPX+ P145E [New Time] E 20 sec. NAVIGATOR P145E > [New Time] E rELAtED oPtions P141E 8E P[MasterCode]E P[InstallerCode]E P145E [NewTime] E SMS* Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
P122E is one of several options which control the behaviour of the AUX2 output. Installer One of the most powerful features of the D8XCEL/D16XCEL panels is the flexibility to FACtory DEFAULt control the AUX outputs by various events and alarms. If the AUX2 output does not behave 1E on.
Select 1 to 99 seconds. FACtory DEFAULt KPX+ P146E [New Time] E 20 sec. P146E > [New Time] E NAVIGATOR rELAtED oPtions P142E 8E SMS* P[MasterCode]E P[InstallerCode]E P146E [NewTime] E Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
This option enables an access control reader to pulse Aux3 when a valid access card is P318E, P328E, P338E, P319E, P329E, presented. Set the reader using P318E, P328E or P338E. P339E. * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 68
Select 1 to 99 seconds. FACtory DEFAULt KPX+ P147E [New Time] E 20 sec. P147E > [New Time] E NAVIGATOR rELAtED oPtions P143E 8E SMS* P[MasterCode]E P[InstallerCode]E P147E [NewTime] E Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
This option enables an access control reader to pulse AUX4 when a valid access card is P318E, P328E, P338E, P319E, P329E, presented. Set the reader using P318E, P328E or P338E. P339E. * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Aux4 driving an extension sonalert. See P124E 2E. Aux4 driving the Quantum Sonic onboard siren as an extension sonalert. Use 106-013 Relay Board or 100-699 or 106-011 Output Expander NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
P151E 8E Pulse AUX5 SMS* P[MasterCode]E P[InstallerCode]E PxxxE [NewTime] E P152E 8E Pulse AUX6 Or use NessXCEL P153E 8E Pulse AUX7 P154E 8E Pulse AUX8 * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
ON RADIO ZONES. SMS* Or use NessXCEL PRO TIP KPX+ When selecting zones, MEMORy E selects all, 0 E deselects all. * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
2K2. • The keyswitch input (if enabled) always uses a 2K2 resistor regardless of the global EOL resistor value set by P129E. Also see P60E 2E, 3E, page 33. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
SIM card the time is automatically set by the cellular network. If the panel is being used 'offline' without a SIM card then use options P340-P344E to set the clock, page 75. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
P392E 1E to enable/disable the option as required NAVIGATOR P392E > enable/disable 1E as required SMS* P[MasterCode]E P[InstallerCode]E P392E 1E as required Or use NessXCEL * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 76
P354E 8E AUx2 Pulse. Turns on the AUX2 output for a time period set P146E. Note. AUX outputs must be enabled for control by AutoTimers at options P121E-P124E. * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
• Signal strength of Radio Keys can The Radio Signal Strength Test can be used to test the radio signal from any Ness radio be tested in USER PROGRAM Mode or device. The strength of the radio signal received is displayed on the zone lights 1 to 8 INSTALLER PROGRAM Mode.
The optional 100–200 Ness Radio Interface is required for radio devices to operate. not also be programmed to accept a A radio device is any type of Ness transmitter including Radio PIR, Radio Reed radio device. Switches, Radio Smoke Detector.
P201E – P256E Each of the 56 User Codes, except for the Master Code, can be programmed to be Radio Codes. This allows up to 55 Ness Radio Keys to be used for Arming and ProgrAm moDE LEVEL Disarming of the panel. The Ness RKP Radio Keypad can also be used with the Installer D8/D16, (see the RKP installer manual).
7E ON: Send test ASCII string. Sends test data periodically, used for testing the serial port (D8x/D16x V6 and later.) * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
When the keypad displays , present the card to a reader. READy TO RECEIVE / OK NORMALLY CLOSED Zone 8 Input Momentary pushbutton * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8X / D16X DELUXE CONTROL PANEL – INSTALLATION MANUAL...
OFF (Use one reader). data is then sent in an extended format that includes the reader address. (Use up to three Ness prox readers). The reader's address is determined the connection of the violet wire. notEs See the wiring diagram on page 86).
Page 83
P[MasterCode]E P[InstallerCode]E P304E [NewValue] E P121E 7E DOTL Alarms to AUX1 P122E 7E DOTL Alarms to AUX1 Or use NessXCEL P305E Misc DOTL options * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8X / D16X DELUXE CONTROL PANEL – INSTALLATION MANUAL...
Page 84
ULTRAPROX READER 1 OUTPUT TIME 01–24 seconds P329E ULTRAPROX READER 2 OUTPUT TIME 01–24 seconds P339E ULTRAPROX READER 3 OUTPUT TIME 01–24 seconds * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 85
Enable options 1-8 as required to assign Reader 3 to Aux outputs as per the table above. P121E 8E, P122E 8E, P123E 8E, P124E 8E, P151E 7E, P152E 7E, P153E 7E, P154E 7E, P319E, P329E, P339E * SMS programming shows the full SMS string to send. KPX+ and NAVIGATOR programming assumes the panel is already in program mode. NESS D8X / D16X DELUXE CONTROL PANEL – INSTALLATION MANUAL...
2. Set P318E, P328E, P338E options to select appropriate AUX outputs. 3. Set corresponding P121E, P122E, P123E, P124E options to 8E. setup Example: • User Codes 1555, 2555, 3555 are programmed to be Code Only Arm and are not assigned to Area 1 or Area 2. • P318E 1E, P328 2E, P338 3E are programmed to set reader output to selected Aux output. • P121E 8E, P122E 8E, P123E 8E are programmed to set AUX outputs to reader. operation Example: • Code 1555 activates door associated with AUX1 (READER 1). • Code 2555 activates door associated with AUX2 (READER 2). • Code 3555 activates door associated with AUX3 (READER 3). NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 88
Disable Mains Fail Alarm All options can be programmed in Installer Program Mode Exit BEEPS - Full Arm Options relating to SMS reporting are marked Exit BEEPS - Home Mode NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Page 89
Zone alarms to AUX1 (p58e selects zones) Zone Supervision alarms to AUX1 Radio key Panic TOGGLE Radio key Panic PULSE door Open Too Long (dOTL) alarm to aUX1 Reader [x] output to AUX1 NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
Maximum 500mA. DIMENSIONS PLASTIC HOUSING 235w x 300h x 90d mm CARTON 330w x 310h x 105d mm CARTON WEIGHT (Plastic Housing) ~ 4kg including plug pack and battery NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
- While the dialler is disabled, the keypad/s will show Signal Strength level 0 (zero) even if a SIM card remains fitted. P17, added Toggle Over-ride commands Z & U instALLEr's notEs NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1...
DATE PURCHASED: DATE INSTALLED: INSTALLATION RECORD INSTALLATION COMPANY: TELEPHONE: MONITORING COMPANY: NESS D8 ALARM CONTROL PANEL TELEPHONE: NESS D16 ALARM CONTROL PANEL P26E ENTRY DELAY TIME 1 Seconds ZONE ASSIGNMENT P27E ENTRY DELAY TIME 2 Seconds P28E EXIT DELAY TIME...