Zone Assignment - Ness D8xD Installer Manual

Deluxe alarm control panel
Table of Contents

Advertisement

P r o g r A m m i n g
ZONe DelAy TyPeS
Only one option per zone can be
selected. For example; a zone cannot
be instant and delayed at the same.
P39e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
All OFF: No Double Trigger zones.
notes
• Double Trigger is useful for preventing
unwanted alarms from zones in harsh
environments such as sheds and
garages.
• 0e will turn all selections OFF.
MeMory e will turn all selections ON.
P40e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
D8, 3e–8e ON: Zones 3–8 are Instant.
D16, 3e–16e ON: Zones 3–16 are
Instant.
notes
• When a zone is selected for this type, it
is automatically deselected from any other
zone type in the DelAy GROUP .
P41e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
1e ON: Zone 1 has entry Delay1.
notes
• The keypad sonalert will beep during
entry Delay as a reminder to disarm the
panel. entry beeps can be disabled by
program option P60e 1e.
• When a zone is selected for this type, it
is automatically deselected from any other
zone type in the DelAy GROUP .
18
Option No.
Description
P39e
DOUBle TRIGGeR zones
P40e
INSTANT zones
P41e
eNTRy DelAy 1 zones
P42e
HANDOVeR zones
P43e
eNTRy DelAy 2 zones
P44e
lOCKOUT zones (Reset O/P) ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON
P45e
AReA 1 zones
P46e
AReA 2 zones
P51e
HOMe zones
P52e
24HR zones
P53e
DAy zones
DoUble trigger Zones
Zones programmed to Double Trigger will recognise an alarm condition if:
• The zone has been triggered twice within a 4 minute period.
• If any 2 zones (both programmed for double trigger), each trigger once.
• The zone is left unsealed for longer than 15 seconds.
PROGRAMMING SeQUeNCe:
P39e [Zone no]e toggles the options ON and OFF
[Zone no] oFF: the zone is not a Double trigger zone
[Zone no] on: the zone is a Double trigger zone
instAnt Zones
Instant Zones operate only in the Armed state. When Armed at the expiry of exit time,
Instant Zones will activate assigned outputs immediately when triggered.
PROGRAMMING SeQUeNCe:
P40e [Zone no]e turns the options ON
[Zone no] on: the zone is an instant Zone
to deselect the option, select a different zone type in the DeLaY grouP .
entry DelAy1 Zones
entry Delay1 zones operate only in the Armed state. When Armed, at the expiry of exit
time these zones will activate the entry Delay Timer1 (P26e) when they are triggered.
If the panel is not disarmed before the expiry of the entry Delay Timer1, the alarm
outputs will be activated.
PROGRAMMING SeQUeNCe:
P41e [Zone no]e turns the options ON
[Zone no] on: the zone is an entry Delay1 zone
to deselect the option, select a different zone type in the DeLaY grouP .
NeSS D8X / D16X DelUXe CONTROl PANel – INSTAllATION MANUAl
ZONeS 1–8 (D8 & D16)
1
2
3
4
5
6
7
8
ON ON ON ON ON ON ON ON ON ON ON ON ON ON
ON
ON
ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON
ZONeS 9–16 (D16)
9 10 11 12 13 14 15 16