Tamper/Keypad Panic Output Mapping - Ness D8xD Installer Manual

Deluxe alarm control panel
Table of Contents

Advertisement

P r o g r A m m i n g
P61e 1e–4e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
1e–4e, ON: Tamper alarm triggers all
outputs.
notes
• A Tamper Alarm can be caused by the
TAMP input or by removing the the J1
PROG/TAMP link on the main board.
P61e 5e–8e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
5e–8e, ON: Panic alarm triggers all
outputs.
notes
• A Keypad Panic Alarm can be caused
by the PANIC keys on the keypad (* e
or ** together, depending on Option
P126e1e).
26
Option No.
P61e
1e
2e
3e
4e
5e
6e
7e
8e
tAmPer AlArm / oUtPUt mAPPing
This option selects which outputs will trigger when a Tamper Alarm occurs.
PROGRAMMING SeQUeNCe:
P61e 1e–4e toggles the options ON and OFF
1e on: tamper alarm to reset output
2e on: tamper alarm to Strobe output
3e on: tamper alarm to Keypad Sonalert output
4e on: tamper alarm to Siren output
keyPAD PAniC AlArm / oUtPUt mAPPing
This option selects which outputs will trigger when a Keypad Panic alarm occurs.
PROGRAMMING SeQUeNCe:
P61e 5e–8e toggles the options ON and OFF
5e on: Keypad Panic alarm to reset output
6e on: Keypad Panic alarm to Strobe output
7e on: Keypad Panic alarm to Keypad Sonalert output
8e on: Keypad Panic alarm to Siren output
NeSS D8X / D16X DelUXe CONTROl PANel – INSTAllATION MANUAl
Description
Tamper to ReSeT output
Tamper to STROBe output
Tamper to Keypad Sonalert
Tamper to SIReN output
Keypad Panic to ReSeT output
Keypad Panic to STROBe output
Keypad Panic to Sonalert
Keypad Panic to SIReN output
Default
ON
ON
ON
ON
ON
ON
ON
ON

Hide quick links: