3 Functions of NB-Designer

3-6-16 Indirect Window

Indirect Window can make an already created window pop up on the current screen. Please
refer to [3-4-3 Window Creation]. Generally, the window called by the indirect window is smaller than the
full screen (but it can also be of the same size as the full screen). The popup window through the
indirect window is the window corresponding to the value of the word address register of [Read
Address]. There is no absolute limitation on the number of indirect windows in NB-Designer. However, a
maximum of 16 popup windows can be displayed simultaneously during operation.
Value 0 is used to close the window, and value -1 means to make Frame 0 pop up, while the values
other than 0 or -1 mean to make the corresponding windows pop up.
3-142
Multiple state
setting, write
Indirect windows,
address is LW100,
read address is
setting mode is
LW100.
"Set Constant"
Press this button,
popup window 20
window 20
window 21
Press this button,
popup window 21